ZHOU Lijun, LIN Tong, JIANG Feiming, et al. Application Research of Autotransformer Winding Fault by Using FRA Multi-decomposition and Image Features[J]. 2021, 47(10): 3617-3627.
ZHOU Lijun, LIN Tong, JIANG Feiming, et al. Application Research of Autotransformer Winding Fault by Using FRA Multi-decomposition and Image Features[J]. 2021, 47(10): 3617-3627.DOI:
Autotransformer(AT) is one of the key devices of high-speed railway power supply system. Split winding structures are adopted for impedance requirements in high-speed railway AT
which are connected inside transformer.Frequency response analysis(FRA) curve of each split winding cannot be directly measured
thus it is difficult for the existing FRA model and diagnostic method to distinguish the faults. In this paper
the method of FRA interpretation based on multi-decomposition and image features is proposed to obtain more information on the frequency response curves
which helps to analyze the small changes. Verification and analysis are carried out by conducting series capacitance variation(SCV) experiments on different windings and different positions in the split winding AT. The results show that the multi-level decomposition FRA curve has a strong correlation with original FRA curve. After being converted into a polar coordinate graph
the graph is different under different fault conditions. The features correlation degree(FCD) values of different fault windings are obviously different
and different faults have their corresponding laws. According to the 12 image features extracted from polar graph and corresponding features correlation after seven-level decomposition
the SCV at different fault windings
fault locations and fault degrees in autotransformer can be distinguished.