The thermal properties of the insulating gas in a gas insulated metal-enclosed transmission line (GIL) will affect the overall insulation performance of the GIL.At present
domestic and foreign research on the application of C
4
F
7
N/CO
2
mixed environmentally friendly gas to GIL has just started
and its thermal characteristics are still un
clear.Therefore
we established a temperature-fluid multi-physical field coupling simulation model for the environment-friendly UHV C
4
F
7
N/CO
2
mixed gas GIL and conducted simulation research.An on-site temperature rise test to effectively verify the model was also conducted.The research results indicate that the internal temperature gradient of environmental-friendly GIL is larger than that of SF
6
GIL
which should be paid attention to in the subsequent design of environmental-friendly GIL.The convection performance of SF
6
is better than that of C
4
F
7
N/CO
2
mixed gas
which will cause differences of temperature distribution in GIL.The relationship between the temperature rise of GIL center conductor and the top of the C
4
F
7
N/CO
2
GIL shell is explored
and the GIL conductor-case temperature rise response coefficient is defined.This coefficient can be applied to the subsequent center conductor temperature monitoring system based on the shell temperature.