超/特高压架空输电线路短路接地线烧伤分析

Research on Electricity Burn of Shorting Grounding Wires in EHV and UHV Transmission Lines

  • 摘要: 通过EMTP仿真计算,分析了淮南—皖南—浙北—上海1 000 kV交流同塔双回线路单回停电时的感应电压和感应电流,结合接地线服役情况,发现停电线路上的感应电压过大,以及接地线挂设过程中存在的反复拉弧放电是造成接地线烧伤的主要原因。利用模拟试验,在计算得到的最大感应电压下,对搭接接地线过程中的电弧进行试验研究,得到电弧能量对导线及工器具影响的临界值,通过引入消弧技术有效地解决了烧伤问题,为输电线路检修人员的作业安全提供了保障。

     

    Abstract: Based on EMTP simulation, an analysis is made on the induced voltage and induced current of the 1 000 kV AC double circuit lines on the same tower of the Huainan-Wannan-Zhebei-Shanghai transmission project with one circuit blackout. According to the service condition of grounding wires, it is found that the main causes for grounding wire burns are the excessive induced voltage on the blackout line and the repeated arc discharge during installation of the grounding wires. Under the maximum induced voltage calculated by simulation, the arc produced in the process of installing grounding wires is studied through test, and the critical value of arc energy which can have impact on the wire and equipment is obtained. The burn problem is effectively solved by introducing arc suppression technology, which guarantees the safety of maintenance personnel.

     

/