余斌, 尹项根, 朱维钧, 吴小忠, 宁春海, 李辉, 龚汉阳, 徐浩, 刘海峰. 复合接地消弧方式接地故障分析及保护对策[J]. 中国电力, 2018, 51(12): 72-79. DOI: 10.11930/j.issn.1004-9649.201803018
引用本文: 余斌, 尹项根, 朱维钧, 吴小忠, 宁春海, 李辉, 龚汉阳, 徐浩, 刘海峰. 复合接地消弧方式接地故障分析及保护对策[J]. 中国电力, 2018, 51(12): 72-79. DOI: 10.11930/j.issn.1004-9649.201803018
Bin YU, Xianggen YIN, Weijun ZHU, Xiaozhong WU, Chunhai NING, Hui LI, Hanyang GONG, Hao XU, Haifeng LIU. Grounding Fault Analysis and Protection Scheme Study for Composite Grounding Arc-suppression Mode[J]. Electric Power, 2018, 51(12): 72-79. DOI: 10.11930/j.issn.1004-9649.201803018
Citation: Bin YU, Xianggen YIN, Weijun ZHU, Xiaozhong WU, Chunhai NING, Hui LI, Hanyang GONG, Hao XU, Haifeng LIU. Grounding Fault Analysis and Protection Scheme Study for Composite Grounding Arc-suppression Mode[J]. Electric Power, 2018, 51(12): 72-79. DOI: 10.11930/j.issn.1004-9649.201803018

复合接地消弧方式接地故障分析及保护对策

Grounding Fault Analysis and Protection Scheme Study for Composite Grounding Arc-suppression Mode

  • 摘要: 论述了配电网中性点典型接地方式和复合接地消弧方式的接线形式。围绕单相接地故障分析,在广泛调研和梳理10 kV配电网典型网络结构及接入设备基础上,遵循现有电力设计标准规范,建立了反映配电网工程实际的精准仿真模型。分别阐述了转移接地方式和智能接地方式的工作原理,仿真分析了其故障处理过程,并提出一种利用本线路故障接地和操作接地的暂态信号首半波接地故障进行选线的方法,同时分析了过渡电阻对智能多模接地方式下零序电流保护的影响,为复合接地消弧方式的工程应用奠定了坚实的理论基础。

     

    Abstract: The wiring form of typical grounding mode and composite grounding arc-suppression mode of distribution network neutral point are discussed. Centering on analysis of single-phase ground fault, and based on a wide-range survey of typical structure and accessing equipment of 10 kV distribution network, accurate simulation model reflecting engineering practice is established according to the existing power design standards. This paper not only describes the principle of grounding fault transfer mode and intelligent multimode grounding mode respectively, but also analyzes their fault treatment process by simulation. In addition, a line selection method based on the first transient half wave of fault grounding and operation grounding of the own line is put forward for grounding fault transfer mode, and the effect of transition resistance on zero-sequence current protection for intelligent multimode grounding mode is analyzed. This research lays a solid theoretical foundation for the engineering application of composite grounding arc-suppression mode.

     

/

返回文章
返回