周桐, 杨庆, 罗庆亮, 王科, 王地陆. 配电线路雷击断线过程中的交流电弧侵蚀研究[J]. 中国电机工程学报, 2025, 45(10): 4077-4089. DOI: 10.13334/j.0258-8013.pcsee.232819
引用本文: 周桐, 杨庆, 罗庆亮, 王科, 王地陆. 配电线路雷击断线过程中的交流电弧侵蚀研究[J]. 中国电机工程学报, 2025, 45(10): 4077-4089. DOI: 10.13334/j.0258-8013.pcsee.232819
ZHOU Tong, YANG Qing, LUO Qingliang, WANG Ke, WANG Dilu. Research on AC Arc Erosion During Lightning Disconnection of Distribution Lines[J]. Proceedings of the CSEE, 2025, 45(10): 4077-4089. DOI: 10.13334/j.0258-8013.pcsee.232819
Citation: ZHOU Tong, YANG Qing, LUO Qingliang, WANG Ke, WANG Dilu. Research on AC Arc Erosion During Lightning Disconnection of Distribution Lines[J]. Proceedings of the CSEE, 2025, 45(10): 4077-4089. DOI: 10.13334/j.0258-8013.pcsee.232819

配电线路雷击断线过程中的交流电弧侵蚀研究

Research on AC Arc Erosion During Lightning Disconnection of Distribution Lines

  • 摘要: 配电线路雷击断线事故严重威胁电网供电质量和安全,电弧作为雷击断线的直接原因,深入研究其侵蚀特性对揭示雷击断线机理具有重要意义。该文开展10 kV系统典型雷击单相接地故障电弧(小电流)和三相短路故障电弧(大电流)对导线的侵蚀研究,在实验室中搭建10 kV配电网单相接地故障模拟实验平台,开展小电流电弧对导线的侵蚀实验。同时,建立相间短路故障下大电流电弧对导线的侵蚀仿真模型,分析大电流电弧对导线的侵蚀效果。结果表明:当雷击引发单相接地故障时,产生的小电流电弧在持续作用40 min将导致导线断股,该时长短于配电网系统单相接地故障允许的最大运行时间阈值。相间短路大电流电弧对导线侵蚀程度随弧长和电流的增大而越发严重,5 kA峰值的大电流电弧可在91 ms完全熔断导线,该时长短于一般配电网断路器速断保护动作时间。

     

    Abstract: Lightning-induced conductor breakage accidents in distribution lines severely threaten power supply quality and grid safety. As arc discharge is the direct cause of such failures, in-depth investigation of its erosion characteristics is crucial for revealing the mechanism of lightning-induced conductor damage. This study investigates the erosion effects on conductors caused by two typical lightning-induced arcs in 10 kV systems: single-phase grounding fault arcs (low current) and three-phase short-circuit fault arcs (high current). A laboratory platform simulating 10 kV single-phase grounding faults is established to conduct low-current arc erosion experiments. Additionally, a simulation model for high-current arc erosion under phase-to-phase short-circuit conditions is developed to analyze the conductor degradation effects. Results indicate that low-current arcs produced by lightning-initiated single-phase grounding faults cause conductor strand breakage sustained action for 40 minutes, a duration shorter than the maximize permissible operating time threshold for such faults in distribution networks. High-current arcs from phase-to-phase short circuits exhibit intensified conductor erosion with increasing arc length and current magnitude. A high-current arc with a 5 kA peak can completely melt the conductor within 91 ms, which is shorter than the typical instantaneous trip protection operation time of distribution circuit breakers.

     

/

返回文章
返回