顾和荣, 胡雨晗, 周晗, 温海军. 微电网对称故障条件下差异性潮流补偿控制策略[J]. 中国电机工程学报, 2024, 44(15): 5985-5995. DOI: 10.13334/j.0258-8013.pcsee.230366
引用本文: 顾和荣, 胡雨晗, 周晗, 温海军. 微电网对称故障条件下差异性潮流补偿控制策略[J]. 中国电机工程学报, 2024, 44(15): 5985-5995. DOI: 10.13334/j.0258-8013.pcsee.230366
GU Herong, HU Yuhan, ZHOU Han, WEN Haijun. A Control Strategy With Differential Power-flow Compensating of Microgrid Under Symmetrical Fault Conditions[J]. Proceedings of the CSEE, 2024, 44(15): 5985-5995. DOI: 10.13334/j.0258-8013.pcsee.230366
Citation: GU Herong, HU Yuhan, ZHOU Han, WEN Haijun. A Control Strategy With Differential Power-flow Compensating of Microgrid Under Symmetrical Fault Conditions[J]. Proceedings of the CSEE, 2024, 44(15): 5985-5995. DOI: 10.13334/j.0258-8013.pcsee.230366

微电网对称故障条件下差异性潮流补偿控制策略

A Control Strategy With Differential Power-flow Compensating of Microgrid Under Symmetrical Fault Conditions

  • 摘要: 独立微电网负荷侧发生故障将导致故障区域功率供需失衡及电压跌落,在具有较高馈线阻感比的微电网中采用传统无功补偿的方法并不能有效解决上述问题。为此,提出一种基于微源馈线阻抗的差异性潮流补偿控制策略,即利用微源冗余功率增加有功功率输出补偿故障区域所需潮流,以改善故障区域功率平衡并抑制电压跌落,同时基于各微源馈线阻抗的差异性计算潮流补偿系数并根据故障区域所需功率动态调整潮流补偿参考值,以优化故障潮流分布并减少馈线损耗。最后,通过仿真和实验验证所提控制策略的有效性。

     

    Abstract: A fault on the load side of an independent microgrid will lead to an imbalance of power supply and demand in the fault area and a voltage drop. The traditional reactive compensation method cannot effectively solve the above problems in the microgrid with a high feeder impedance to inductance ratio. This paper proposes a control strategy with differential power-flow compensating based on micro-source feeder impedance. This approach uses micro-source redundant power to compensate the power flow required in the fault area by increasing the active power output, thereby improving the power balance in the fault area and suppressing the voltage drop. The power flow compensation coefficient is calculated based on the difference of each micro-source feeder impedance and the reference value of power flow compensation is dynamically adjusted according to the power required in the fault area to optimize the distribution of fault power flow and reduce feeder losses. Finally, the effectiveness of the proposed control strategy is verified by simulation and experiment.

     

/

返回文章
返回