周万迪, 郭亮, 魏晓光, 高冲, 贺之渊, 张升. 混合式直流断路器合成开断试验方法及等效研究[J]. 中国电机工程学报, 2022, 42(14): 5233-5241. DOI: 10.13334/j.0258-8013.pcsee.210388
引用本文: 周万迪, 郭亮, 魏晓光, 高冲, 贺之渊, 张升. 混合式直流断路器合成开断试验方法及等效研究[J]. 中国电机工程学报, 2022, 42(14): 5233-5241. DOI: 10.13334/j.0258-8013.pcsee.210388
ZHOU Wandi, GUO Liang, WEI Xiaoguang, GAO Chong, HE Zhiyuan, ZHANG Sheng. Synthetic Breaking Test Method and Equivalence Analysis of Hybrid DC Circuit Breakers[J]. Proceedings of the CSEE, 2022, 42(14): 5233-5241. DOI: 10.13334/j.0258-8013.pcsee.210388
Citation: ZHOU Wandi, GUO Liang, WEI Xiaoguang, GAO Chong, HE Zhiyuan, ZHANG Sheng. Synthetic Breaking Test Method and Equivalence Analysis of Hybrid DC Circuit Breakers[J]. Proceedings of the CSEE, 2022, 42(14): 5233-5241. DOI: 10.13334/j.0258-8013.pcsee.210388

混合式直流断路器合成开断试验方法及等效研究

Synthetic Breaking Test Method and Equivalence Analysis of Hybrid DC Circuit Breakers

  • 摘要: 国际上已开发出多种混合式高压直流断路器,并完成工程应用,其在多端和直流电网应用前景广阔。短路电流开断能力是直流断路器的核心性能,而直流开断过程同时存在大电流、高电压和强能量,造成在试验室中等效复现开断应力极为困难。国际上至今尚未形成统一的等效开断试验标准,试验容量与等效性关系也缺少理论研究和定量分析。该文基于混合式直流断路器开断原理,提取开断过程分阶段等效应力,揭示试验容量与等效性数学关系,奠定试验电路参数设计及等效分析的理论基础。进一步提出双频电流源合成开断试验方法,完成关键等效应力数学解析与试验电路参数最优设计,开展试验应力仿真验证及等效性对比分析。研究表明,双频电流源合成等效试验方法可实现混合式直流断路器开断电应力全等效,技术经济性良好,对开断试验装置开发及标准制定具有指导意义。

     

    Abstract: A variety of hybrid high voltage direct current (HVDC) circuit breakers were developed worldwide and have been successfully put into operation, which have broad application prospects in multi-terminal and DC power grids. Short-circuit current breaking capability is the core performance of DC circuit breakers (DCCB). However, large current, high voltage and huge energy appear simultaneously during the breaking process, which makes it extremely difficult to reproduce the equivalent breaking stress in the laboratory. So far, there is still no uniform international standard for the breaking test, and lack of theoretical research and calculation on the relationship of test capacity and equivalence. Based on the breaking principle of hybrid DCCBs, this paper analyzed the equivalent stresses at each breaking stage, and revealed the mathematical relationship on test capacity and equivalence which supporting the test parameters design and equivalence analysis. Then a dual-frequency current source synthetic breaking test method was proposed, and the key stress mathematical analysis and the test circuit parameters optimal design were achieved. Finally, simulation and comparative analysis for the test stress and equivalence were carried out. The research shows that the dual-frequency current source synthetic test method can realize the full equivalent of the breaking electrical stresses of hybrid DCCBs with good economic performance, and have great guiding significance for the equipment development and standards formulation of hybrid DCCB breaking test.

     

/

返回文章
返回