裴春明, 陈豫朝, 陈小月, 蓝磊, 肖国洲, 文习山. 交流电晕笼无线电干扰试验校准系数研究[J]. 中国电机工程学报, 2015, 35(24): 6566-6572. DOI: 10.13334/j.0258-8013.pcsee.2015.24.034
引用本文: 裴春明, 陈豫朝, 陈小月, 蓝磊, 肖国洲, 文习山. 交流电晕笼无线电干扰试验校准系数研究[J]. 中国电机工程学报, 2015, 35(24): 6566-6572. DOI: 10.13334/j.0258-8013.pcsee.2015.24.034
PEI Chunming, CHEN Yuchao, CHEN Xiaoyue, LAN Lei, XIAO Guozhou, WEN Xishan. Research on Measurement Calibration Coefficient of Radio Interference With AC Corona Cages[J]. Proceedings of the CSEE, 2015, 35(24): 6566-6572. DOI: 10.13334/j.0258-8013.pcsee.2015.24.034
Citation: PEI Chunming, CHEN Yuchao, CHEN Xiaoyue, LAN Lei, XIAO Guozhou, WEN Xishan. Research on Measurement Calibration Coefficient of Radio Interference With AC Corona Cages[J]. Proceedings of the CSEE, 2015, 35(24): 6566-6572. DOI: 10.13334/j.0258-8013.pcsee.2015.24.034

交流电晕笼无线电干扰试验校准系数研究

Research on Measurement Calibration Coefficient of Radio Interference With AC Corona Cages

  • 摘要: 电晕笼无线电干扰试验得到的导线激发函数应进行校准等效之后再应用于输电线路的无线电干扰计算中。校准系数通常通过校准试验获得,但校准实验的准确性受试验条件和环境的影响。若能通过理论分析代替校准试验得到较为精确的校准系数,会更加经济和便捷。该文基于电路分析方法,建立电晕笼试验回路的分布参数模型,依据电晕放电脉冲在空间和时间上的独立性,通过求取放电点不同位置时校准系数的响应曲线计算得到校准系数,并与分段电容获得的理论校准系数进行对比分析。结果表明,校准系数的理论分析模型可以较好地应用于电晕笼试验和实际线路无线电干扰计算之间的等效,且兼具经济性和实用性。

     

    Abstract: The excitation function measured from radio interference test corona cages should be calibrated before being applied to radio interference calculation of the transmission line. The calibration factor is usually obtained by calibration experiments. However, the accuracy of calibration experiments is affected by the test condition and environment. This paper analyzed the theoretical calibration factor based on the circuit analysis method, which is more economic and convenient than calibration experiments. The distributed parameter model of the corona cage test circuit was established, and according to the independence of the corona discharge pulse in space and time, curves of the calibration coefficient for the corona discharge source at different position were obtained. Thus, the calibration coefficient was calculated, which was compared with the one obtained from proportion of capacitance. The results showe that the theoretical analysis method presented can be applied to calibrate the excitation function from corona cage tests, and it is economical and practical.

     

/