赵竞涵, 于淼, 刘佳宁, 王晓明. 基于分散式阻抗判据的多换流器接入交流微电网稳定性分析[J]. 中国电机工程学报, 2021, 41(10): 3575-3584. DOI: 10.13334/j.0258-8013.pcsee.200898
引用本文: 赵竞涵, 于淼, 刘佳宁, 王晓明. 基于分散式阻抗判据的多换流器接入交流微电网稳定性分析[J]. 中国电机工程学报, 2021, 41(10): 3575-3584. DOI: 10.13334/j.0258-8013.pcsee.200898
ZHAO Jinghan, YU Miao, LIU Jianing, WANG Xiaoming. Decentralized Impedance Criteria for Stability Analysis of Multi-converter AC Microgrid[J]. Proceedings of the CSEE, 2021, 41(10): 3575-3584. DOI: 10.13334/j.0258-8013.pcsee.200898
Citation: ZHAO Jinghan, YU Miao, LIU Jianing, WANG Xiaoming. Decentralized Impedance Criteria for Stability Analysis of Multi-converter AC Microgrid[J]. Proceedings of the CSEE, 2021, 41(10): 3575-3584. DOI: 10.13334/j.0258-8013.pcsee.200898

基于分散式阻抗判据的多换流器接入交流微电网稳定性分析

Decentralized Impedance Criteria for Stability Analysis of Multi-converter AC Microgrid

  • 摘要: 对于交流微电网的稳定性分析,传统方法如时域特征值分析或频域的奈奎斯特判据等,在模块化微电网中应用时,随着模型维度增长计算量大大增加,且无法有效指导交流微电网子系统设计和控制参数调优工作。针对这一局限,该文提出一种基于分散式阻抗判据的交流微电网稳定性分析方法,通过Park变换和解耦控制,将交流微电网转化为2个独立等效直流子系统,然后由各子系统的额定母线电压和额定容量推导得出各子系统的恒定阻抗判据。基于所提分散式阻抗判据,可以在实现对系统模块化设计的同时,保证交流微电网的整体稳定性,最后通过MATLAB/Simulink仿真对所提方法有效性进行了验证。

     

    Abstract: For the stability analysis of AC microgrids, the conventional methods including the eigenvalue analysis in time domain or Nyquist Criterion in frequency domain are facing curse of dimensionality in modular application and unable to give effective instructions independently for the design of the subsystem of AC microgrid and the control parameter tuning. Aiming at this problem, this paper proposed a decentralized impedance-based method for the stability analysis of AC microgrid, in which the AC microgrid was transformed into two decoupled DC subsystems by Park transformation and decoupling control. Then the invariant impedance specifications were defined for each subsystem in terms of the rated bus voltage and rated capacity of each subsystem. Based on the decentralized impedance-based criteria, a modular design can be realized and the overall stability of AC microgrid can be guaranteed at the same time. The effectiveness of the proposed method was verified by MATLAB/Simulink simulation.

     

/