薛永端, 陈梦琦, 曹丽丽, 冯光, 徐丙垠. 不接地系统单相断线故障电压分析[J]. 中国电机工程学报, 2021, 41(4): 1322-1333. DOI: 10.13334/j.0258-8013.pcsee.191665
引用本文: 薛永端, 陈梦琦, 曹丽丽, 冯光, 徐丙垠. 不接地系统单相断线故障电压分析[J]. 中国电机工程学报, 2021, 41(4): 1322-1333. DOI: 10.13334/j.0258-8013.pcsee.191665
XUE Yongduan, CHEN Mengqi, CAO Lili, FENG Guang, XU Bingyin. Analysis of Voltage Characteristics of Single-phase Disconnection Fault in Ungrounded Distribution System[J]. Proceedings of the CSEE, 2021, 41(4): 1322-1333. DOI: 10.13334/j.0258-8013.pcsee.191665
Citation: XUE Yongduan, CHEN Mengqi, CAO Lili, FENG Guang, XU Bingyin. Analysis of Voltage Characteristics of Single-phase Disconnection Fault in Ungrounded Distribution System[J]. Proceedings of the CSEE, 2021, 41(4): 1322-1333. DOI: 10.13334/j.0258-8013.pcsee.191665

不接地系统单相断线故障电压分析

Analysis of Voltage Characteristics of Single-phase Disconnection Fault in Ungrounded Distribution System

  • 摘要: 随着架空绝缘导线的普及,断线故障已成为配电网常见故障之一。该文以不接地系统为对象,建立单相断线故障模型,综合考虑故障类型(断线不接地、断线并电源侧/负荷侧接地)、故障线路对地电容占比、断线位置、负载阻抗大小和坠地点接地电阻大小等影响因素,分析地电位与中性点(零序)电压偏移规律,进一步推导断口前后三相电压和线电压的幅值、相位以及相序变化特征,并与不接地系统单纯小电流接地故障的电气特征进行对比,利用数字仿真验证了分析结果的正确性。该文结果可为利用电压信号的配电网断线故障检测及定位方法研究提供理论依据。

     

    Abstract: With wide application of overhead insulated lines, the disconnection fault has risen to be one of the common faults in distribution networks. In this paper, aiming at ungrounded distribution system, a single-phase disconnection fault model was established. The fault type, including ungrounded fault, disconnected fault and power side or load side grounding fault, as well as the ratio of the capacitance to ground of the fault line, disconnection position, load impedance, grounding resistance of the sinking point, are the factors which was discussed in this paper. By taking these factors into account, the ground potential and zero-sequence voltage offset law at neutral point were analyzed. The changing characteristics of phase sequence, as well as the amplitude and phase of the three-phase voltage and line voltage, before and after the fracture were further deduced. The electrical characteristics of the simple single-phase grounding fault in the ungrounded distribution system were used to make comparison with it. The accuracy of the analysis results was verified by digital simulation. The results of this paper can provide a theoretical basis for the research on the detection and location methods of disconnected faults using voltage signals for distribution network.

     

/