苏鹏飞, 袁艺嘉, 孙亚辉, 林志光, 李元贞. 海上风电用±550 kV直流GIS过电压与绝缘配合研究[J]. 全球能源互联网, 2024, 7(4): 463-472. DOI: 10.19705/j.cnki.issn2096-5125.2024.04.011
引用本文: 苏鹏飞, 袁艺嘉, 孙亚辉, 林志光, 李元贞. 海上风电用±550 kV直流GIS过电压与绝缘配合研究[J]. 全球能源互联网, 2024, 7(4): 463-472. DOI: 10.19705/j.cnki.issn2096-5125.2024.04.011
SU Pengfei, YUAN Yijia, SUN Yahui, LIN Zhiguang, LI Yuanzhen. Research on Overvoltage and Insulation Coordination of±550 kV DC GIS for Offshore Wind Power[J]. Journal of Global Energy Interconnection, 2024, 7(4): 463-472. DOI: 10.19705/j.cnki.issn2096-5125.2024.04.011
Citation: SU Pengfei, YUAN Yijia, SUN Yahui, LIN Zhiguang, LI Yuanzhen. Research on Overvoltage and Insulation Coordination of±550 kV DC GIS for Offshore Wind Power[J]. Journal of Global Energy Interconnection, 2024, 7(4): 463-472. DOI: 10.19705/j.cnki.issn2096-5125.2024.04.011

海上风电用±550 kV直流GIS过电压与绝缘配合研究

Research on Overvoltage and Insulation Coordination of±550 kV DC GIS for Offshore Wind Power

  • 摘要: 海上风电经柔性直流送出已成为风电消纳的重要途径。直流气体绝缘开关设备(gas insulated switchgear,GIS)用于海上风电换流平台,可以降低整体海上换流站平台体积及设备造价,降低了海上设备的运维成本。围绕海上风电用±550 kV直流GIS的过电压与绝缘配合进行研究,首先确定柔直系统的结构与参数、控制保护策略和避雷器配置方案,进而通过仿真获得最大过电压水平,对于不同运行方式下故障极与非故障极的直流极线过电压进行分析,最后明确±550 kV直流GIS中避雷器参数与±550 kV直流GIS设备的绝缘水平要求。

     

    Abstract: The VSC-HVDC transmission of offshore wind power has become an important way for wind power consumption.Direct current gas insulated switchgear (DC GIS) is used for offshore wind power converter platforms,which could reduce the overall platform volume and equipment cost of offshore converter stations,and reduce the operation and maintenance costs of offshore equipment.The overvoltage and insulation coordination of±550 kV DC GIS for offshore wind power have been studied.Firstly,the structure and parameters of VSC-HVDC system are studied.The control and protection strategies,and the configuration of surge arrester are given.Then,the maximum overvoltage level is obtained through the simulation.The DC pole line overvoltage of faulty pole and non-faulty pole under different operation modes are analyzed.Finally,the parameters of the arrester in±550 kV DC GIS and the insulation level requirements of the±550 kV DC GIS are given.

     

/

返回文章
返回