池代波,肖国锋.基于CFD模拟的某柔直换流站户内启动回路场自然通风方案研究[J].南方能源建设,2021,08(04):123-129.. DOI: 10.16516/j.gedi.issn2095-8676.2021.04.016
引用本文: 池代波,肖国锋.基于CFD模拟的某柔直换流站户内启动回路场自然通风方案研究[J].南方能源建设,2021,08(04):123-129.. DOI: 10.16516/j.gedi.issn2095-8676.2021.04.016
CHI Daibo,XIAO Guofeng.Research on Natural Ventilation in the Indoor Pre-Insertion Resistor Circuit Field of the VSC-HVDC Converter Substation Based on CFD[J].Southern Energy Construction,2021,08(04):123-129.. DOI: 10.16516/j.gedi.issn2095-8676.2021.04.016
Citation: CHI Daibo,XIAO Guofeng.Research on Natural Ventilation in the Indoor Pre-Insertion Resistor Circuit Field of the VSC-HVDC Converter Substation Based on CFD[J].Southern Energy Construction,2021,08(04):123-129.. DOI: 10.16516/j.gedi.issn2095-8676.2021.04.016

基于CFD模拟的某柔直换流站户内启动回路场自然通风方案研究

Research on Natural Ventilation in the Indoor Pre-Insertion Resistor Circuit Field of the VSC-HVDC Converter Substation Based on CFD

  • 摘要:
      目的  电网工程采用全户内紧凑型布置是当前国内城市电网建设大力发展形势下的必然趋势。如何将室内设备产生的大量热量散发出去,且减少对周围环境产生不利影响,是一项值得深入研究的课题。自然通风作为经济高效、无噪声产生的通风方案应优先考虑采用。为研究不同气楼方案对户内启动回路场自然通风的影响,在其他条件不变的情况下,通过改变气楼位置及形式,对广州市某直换流站工程户内启动回路场的散热效果进行对比分析。
      方法  采用CFD数值模拟方法,针对流线型通风器和薄型通风器工况,模拟了厂房内气流的温度场和速度场。
      结果  模拟结果显示,采用自然通风方案可行。且流线型气楼相比于薄型气楼,增大了气楼的有效通风面积,优化了室内空气流场,可将户内直流场内部环境温度多降低约2 ℃,可在相同环境温度下达到更好的整体降温效果。
      结论  验证了自然通风散热方案在户内直流场启动回路通风系统应用的可行性,表明流线型气楼通风散热的效果在特定环境中要优于薄型气楼,可为以后类似直换流站工程的通风散热方案选择及气楼优选提供参考和依据。

     

    Abstract:
      Introduction  It is an inevitable trend for the current power grid construction in the urban area in domestic to adopt a compact indoor layout for the whole house in the power grid project. However, how to dissipate a large amount of heat emitted by indoor equipment without adversely affecting the surrounding environment is an issue worthy of in-depth study. As a cost-effective, noise-free ventilation scheme, natural ventilation should be given a priority. In order to study the influence of different schemes on natural ventilation of the indoor pre-insertion resistor circuit when other conditions remain unchanged, by changing the position and form of the ventilators, this paper discusses the cooling method of an indoor pre-insertion resistor circuit field in a VSC-HVDC converter substation in Guangzhou.
      Method  Based on CFD, the temperature field and velocity field of the air flow in the factory building under the conditions of using streamline ventilator and thin ventilator were simulated respectively.
      Result  The result of the simulation show that the natural ventilation scheme is feasible. It can also be verified that the streamlined ventilator increases the effective ventilation area, optimizes the indoor air flow field, reduces the internal ambient temperature of the indoor DC field by about 2 °C more compared with the thin ventilator, and can achieve a better overall cooling effect under the same ambient temperature.
      Conclusion  It can be concluded that natural ventilation of the indoor pre-insertion resistor circuit is proved to be feasible, and heat dissipation effect of the streamlined ventilator is better than that of the thin ventilator in a specific environment. This project can provide reference and basis for similar VSC-HVDC converter substation in the future.

     

/

返回文章
返回