基于广域连接的广东地区接地极连接方案研究

Research on Connection Scheme of HVDC WAN Grounding Electrode In Guangdong Based on Wide-Area Connection

  • 摘要:
      目的  为解决高压直流输电工程中接地极在广东地区选址困难问题,研究将现有接地极连接组成广域接地极供未来直流工程接入,减少对极址周围电气设施、地下金属管道设施的影响。
      方法  分析了现有接地极作为子接地极组成广域接地极的可行性,提出几种典型的广域接地极应用场景,并进行了各子接地极的自然分流计算、均流计算和多回直流同时运行工况计算。
      结果  广域接地极能降低粤东极址的设计要求,缓解鱼龙岭接地极对油气管道和周边电力系统的影响,具有实施的可行性。但在不增加均流电阻的情况下,效益仍不明显。
      结论  该研究为通过采用广域接地极,降低新建接地的难度提供思路和方法。

     

    Abstract:
      Introduction  To solve the problem of difficult site selection for grounding electrodes in HVDC transmission projects in Guangdong, this paper analyzes the connection of existing grounding electrodes to form a WAN grounding electrode for future DC project access to reduce the impact on electrical facilities and underground metal piping facilities around the electrode site.
      Method  The feasibility of forming a wide-area grounding electrode by using existing grounding electrodes as sub-grounding electrodes was analyzed, several typical application scenarios of WAN grounding electrodes were proposed, and the natural shunted current calculation, current distribution averaging and multiple DC simultaneous operation conditions of each sub-grounding electrode were carried out.
      Result  WAN grounding electrode can reduce the design requirements of Yuedong pole site and mitigate the impact of Yulongling grounding electrode on oil and gas pipeline and surrounding power system, and has the feasibility of implementation. However, the benefits are still not obvious without adding any current averaging resistors.
      Conclusion  This study provides ideas and methods to reduce the difficulty of constructing new grounding electrodes by using WAN grounding electrodes.

     

/