林侃,梁石,刘宇穗等.双机回热系统小汽机仪控设计及控制策略研究[J].南方能源建设,2021,08(04):66-72.. DOI: 10.16516/j.gedi.issn2095-8676.2021.04.009
引用本文: 林侃,梁石,刘宇穗等.双机回热系统小汽机仪控设计及控制策略研究[J].南方能源建设,2021,08(04):66-72.. DOI: 10.16516/j.gedi.issn2095-8676.2021.04.009
LIN Kan,LIANG Shi,LIU Yusui,et al.Research on Instrument and Control Design and Control Strategy for Small Steam Turbine in Double-Turbine Regeneration System[J].Southern Energy Construction,2021,08(04):66-72.. DOI: 10.16516/j.gedi.issn2095-8676.2021.04.009
Citation: LIN Kan,LIANG Shi,LIU Yusui,et al.Research on Instrument and Control Design and Control Strategy for Small Steam Turbine in Double-Turbine Regeneration System[J].Southern Energy Construction,2021,08(04):66-72.. DOI: 10.16516/j.gedi.issn2095-8676.2021.04.009

双机回热系统小汽机仪控设计及控制策略研究

Research on Instrument and Control Design and Control Strategy for Small Steam Turbine in Double-Turbine Regeneration System

  • 摘要:
      目的  双机回热系统可以提升机组的能级效率,如何设计双机回热系统的控制策略并确保其安全、经济、有效一直是我们关注的重点问题。
      方法  针对双机回热系统的功能要求,设计了相应的双机回热系统的仪表测点布置方案,并系统性地提出了双机回热小机的启动、转速控制、系统保护及背压控制的策略。
      结果  该双机回热控制策略已在超超临界1 000 MW机组中成功应用,可使双机回热控制系统在满足给水转速控制的同时,也满足双机回热小机的抽汽、排汽,溢流等协调控制要求,以确保系统稳定、可靠、经济运行。
      结论  所提出的控制策略,对后续双机回热系统的控制策略研究具有参考借鉴意义。

     

    Abstract:
      Introduction  The double-turbine regeneration system can improve the energy efficiency of the unit. How to design the control strategy and ensure its safety, economy and effectiveness has been the prime focus of our group.
      Method  According to the functional requirements of the double-turbine regeneration system, a corresponding the scheme of instrument arrangement of measuring points was designed, and a complete set of start-up, speed control, system protection and back pressure control strategies were put forward systematically.
      Result  The control strategy has been successfully applied in a 1 000 MW Ultra Super-critical Pressure Unit, the results show that the control strategy can make the double-turbine regeneration system not only meet the feed water speed control, but also meet the requirements of coordinated control of steam extraction, exhaust and overflow, so as to ensure the stable, reliable and economic operation of the system.
      Conclusion  The proposed control strategy has reference significance for further study on control strategy for double-turbine regeneration system.

     

/