廖才波, 黎凯, 邱志斌, 胡雄, 李童宏飞, 陈则宇. 干式铁芯电抗器振动特性数值模拟及试验研究[J]. 高电压技术, 2024, 50(3): 962-973. DOI: 10.13336/j.1003-6520.hve.20231266
引用本文: 廖才波, 黎凯, 邱志斌, 胡雄, 李童宏飞, 陈则宇. 干式铁芯电抗器振动特性数值模拟及试验研究[J]. 高电压技术, 2024, 50(3): 962-973. DOI: 10.13336/j.1003-6520.hve.20231266
LIAO Caibo, LI Kai, QIU Zhibin, HU Xiong, LI Tonghongfei, CHEN Zeyu. Numerical Simulation and Experimental Research on Vibration Characteristics of Dry-type Iron-core Reactor[J]. High Voltage Engineering, 2024, 50(3): 962-973. DOI: 10.13336/j.1003-6520.hve.20231266
Citation: LIAO Caibo, LI Kai, QIU Zhibin, HU Xiong, LI Tonghongfei, CHEN Zeyu. Numerical Simulation and Experimental Research on Vibration Characteristics of Dry-type Iron-core Reactor[J]. High Voltage Engineering, 2024, 50(3): 962-973. DOI: 10.13336/j.1003-6520.hve.20231266

干式铁芯电抗器振动特性数值模拟及试验研究

Numerical Simulation and Experimental Research on Vibration Characteristics of Dry-type Iron-core Reactor

  • 摘要: 振动是影响干式铁芯电抗器运行状态的关键因素之一。在考虑铁芯夹件、垫块等结构件的影响下,采用有限元法实现了10 kV干式铁芯电抗器的3维瞬态电磁-结构多物理场仿真分析,研究了电抗器在磁致伸缩力、麦克斯韦力与洛伦兹力3者共同作用下的振动位移及速度分布特性。仿真结果表明,正常运行状态下,干式铁芯电抗器铁芯夹件的振动位移及速度显著大于其他部位,尤其是用于固定绕组的穿心螺杆。其次,结合干式铁芯电抗器模态仿真分析,获得了其模态特性及固有频率,并进一步分析了其振动机理。最后,采用多普勒激光测振仪测量了某10 kV干式铁芯电抗器的振动特性。试验结果表明,干式铁芯电抗器的振动频率以100 Hz及其倍频为主,其中300 Hz的振动响应最显著,其与其固有频率较接近,存在一定的共振风险。同时,试验结果与仿真结果一致性较好,验证了该文所述仿真分析方法的正确性和有效性。

     

    Abstract: Vibration is one of the key factors affecting the running status of dry-type iron-core reactor. The influences of structural components such as clamping structure and supporting pads are taken into account, and the three-dimensional transient electromagnetic-structural multi-physics simulation of 10 kV dry-type iron-core reactor based on finite element method is realized in the paper. The vibration displacement and velocity distribution of reactor under the combined influences of magnetostrictive force, Maxwell force and Lorentz force are studied. The simulation results show that, under normal operating conditions, the vibration displacement and speed of the clamping structure of the dry-type iron core reactor are significantly greater than those of other parts, especially the core screws which are used to fix the windings. Then, combined with the modal simulation analysis of the dry-type core reactor, its modal characteristics and inherent frequencies are obtained in the paper, and its vibration mechanism is further analyzed. Finally, the vibration characteristics of a 10 kV dry-type iron-core reactor are measured with a Doppler laser vibration meter. The test results show that the vibration frequency of the dry-type iron-core reactor is mainly 100 Hz and its multiples, the vibration response at 300 Hz is the most significant, which is relatively close to its inherent frequency, and there is a risk of resonance. At the same time, the test results are in good agreement with the simulation results, which verifies the workability and validity of the simulation analysis method proposed in the paper.

     

/

返回文章
返回