戴志辉, 牛宝仪, 邱宏逸, 奚潇睿, 韩哲宇, 韦舒清. 基于初始电流行波相位的多端混合直流线路单端保护方案[J]. 高电压技术, 2024, 50(2): 649-659. DOI: 10.13336/j.1003-6520.hve.20230717
引用本文: 戴志辉, 牛宝仪, 邱宏逸, 奚潇睿, 韩哲宇, 韦舒清. 基于初始电流行波相位的多端混合直流线路单端保护方案[J]. 高电压技术, 2024, 50(2): 649-659. DOI: 10.13336/j.1003-6520.hve.20230717
DAI Zhihui, NIU Baoyi, QIU Hongyi, XI Xiaorui, HAN Zheyu, WEI Shuqing. Single-ended Protection Scheme for Multi-terminal Hybrid DC Lines Based on Initial Current Traveling Wave Phase[J]. High Voltage Engineering, 2024, 50(2): 649-659. DOI: 10.13336/j.1003-6520.hve.20230717
Citation: DAI Zhihui, NIU Baoyi, QIU Hongyi, XI Xiaorui, HAN Zheyu, WEI Shuqing. Single-ended Protection Scheme for Multi-terminal Hybrid DC Lines Based on Initial Current Traveling Wave Phase[J]. High Voltage Engineering, 2024, 50(2): 649-659. DOI: 10.13336/j.1003-6520.hve.20230717

基于初始电流行波相位的多端混合直流线路单端保护方案

Single-ended Protection Scheme for Multi-terminal Hybrid DC Lines Based on Initial Current Traveling Wave Phase

  • 摘要: 为了解决LCC-MMC型多端混合直流系统线路保护存在的问题,提出一种基于初始电流行波相位的多端混合直流线路单端保护方案。首先基于多端混合直流输电线路发生不同位置和类型的故障工况,推导直流线路入射电压行波的解析式并计算其高频段相位。其次结合线路边界行波折反射原理和测量波阻抗特性,提出利用初始电压行波相位的区内外识别判据,并根据雷击和短路故障的入射行波低频相位特性构建雷击干扰判据。在PSCAD/EMTDC中搭建昆柳龙多端混合直流系统模型进行验证,证明所提方案仅利用单端量信息即可满足故障判断和选线要求,满足速度性的同时具备一定的抗过渡电阻能力(500 Ω)。

     

    Abstract: Aiming at the problems existing in the line protection of the existing LCC-MMC multi-terminal hybrid DC system, a single-end protection scheme for multi-terminal hybrid DC lines based on the initial current traveling wave phase is proposed. Firstly, based on the fault conditions of different locations and types of multi-terminal hybrid DC transmission lines, the analytical formula of the traveling wave of the incident voltage of the DC line is derived and its high-frequency phase is calculated. Secondly, based on the principle of traveling wave refraction and reflection at the line boundary and the measured wave impedance characteristics, a criterion for identifying inside and outside the zone using the phase of the initial current traveling wave is proposed. In addition, the lightning strike interference criterion is constructed based on the phase characteristics of the incident traveling wave in the low-frequency band of lightning strikes and short-circuit faults. Finally, a Kunliulong multi-terminal hybrid DC system model is built in PSCAD/EMTDC for simulation verification. The results show that the proposed protection can meet the fault judgment and line selection requirements only by using single-ended quantity information, and has a certain anti-transition resistance capability (500 Ω) while meeting the speed requirement.

     

/

返回文章
返回