边晓燕, 谌云峰, 周歧斌, 张耀, 魏本刚, 童攀. 基于热路解析模型的海底电缆动态温度场计算与短时允许载流量评估[J]. 高电压技术, 2023, 49(2): 793-802. DOI: 10.13336/j.1003-6520.hve.20220667
引用本文: 边晓燕, 谌云峰, 周歧斌, 张耀, 魏本刚, 童攀. 基于热路解析模型的海底电缆动态温度场计算与短时允许载流量评估[J]. 高电压技术, 2023, 49(2): 793-802. DOI: 10.13336/j.1003-6520.hve.20220667
BIAN Xiaoyan, CHEN Yunfeng, ZHOU Qibin, ZHANG Yao, WEI Ben’gang, TONG Pan. Dynamic Temperature Field Calculation and Short-time Allowable Ampacity Evaluation of Submarine Cable Based on Thermal Analytical Model[J]. High Voltage Engineering, 2023, 49(2): 793-802. DOI: 10.13336/j.1003-6520.hve.20220667
Citation: BIAN Xiaoyan, CHEN Yunfeng, ZHOU Qibin, ZHANG Yao, WEI Ben’gang, TONG Pan. Dynamic Temperature Field Calculation and Short-time Allowable Ampacity Evaluation of Submarine Cable Based on Thermal Analytical Model[J]. High Voltage Engineering, 2023, 49(2): 793-802. DOI: 10.13336/j.1003-6520.hve.20220667

基于热路解析模型的海底电缆动态温度场计算与短时允许载流量评估

Dynamic Temperature Field Calculation and Short-time Allowable Ampacity Evaluation of Submarine Cable Based on Thermal Analytical Model

  • 摘要: 准确计算海底电缆动态温度场和短时允许载流量对保障海缆安全运行具有重要意义。针对现有的解析方法无法精确求解海底电缆动态温度场和短时允许载流量的问题,提出一种最优热路解析模型,将海底电缆的本体和埋设环境进行分层建模,推导出可以计算海底电缆外部环境等效热阻、热容的公式;然后采用热电类比法构建海底电缆本体和埋设环境的热路解析模型,并应用控制变量法确定热路解析模型的最优分层数和最优传热半径。最后,以某500 kV型号的交流海底电缆为例,对所提最优热路解析模型进行分析验证。计算结果表明:该最优热路解析模型具有较好的准确性和高效性;基于该模型对海底电缆的短时允许载流量进行评估,计算发现海底电缆短时允许最大载流量与海底电缆的初始稳态电流和过载时间有关。

     

    Abstract: Accurate calculation of dynamic temperature field and short-time allowable ampacity of submarine cables is of great significance to ensure safe operation of submarine cables. Aiming at the problem that the existing analytical methods can not accurately solve the dynamic temperature field and short-time allowable ampacity of submarine cables, an optimal thermal route analytical model is proposed. Building layered model of the cable body and the buried environment, deducing a set of formulas to calculate the equivalent thermal resistance and heat capacity of the external environment of the cable. Then the thermal path analytical model of the cable body and the environment is established by using thermoelectric analogy method. The optimal number of layers and optimal heat transfer radius of thermal path analytical model was selected by using control variable method. Finally, a 500 kV alternating current submarine cable is taken as an example to analyze and verify the proposed optimal thermal route analytical model, and the results show that model has good accuracy and high efficiency. The short-time amperage of submarine cable is evaluated based on the model, which shows that the short-time allowable maximum ampacity of submarine cable is related to the initial steady current and overload time of submarine cable.

     

/

返回文章
返回