吴闽, 蒋伟, 罗颖婷, 沈道义, 杨俊杰. 基于改进SSD的GIS多源局放模式识别[J]. 高电压技术, 2023, 49(2): 812-821. DOI: 10.13336/j.1003-6520.hve.20220400
引用本文: 吴闽, 蒋伟, 罗颖婷, 沈道义, 杨俊杰. 基于改进SSD的GIS多源局放模式识别[J]. 高电压技术, 2023, 49(2): 812-821. DOI: 10.13336/j.1003-6520.hve.20220400
WU Min, JIANG Wei, LUO Yingting, SHEN Daoyi, YANG Junjie. Multi-source Partial Discharge Pattern Recognition in GIS Based on Improved SSD[J]. High Voltage Engineering, 2023, 49(2): 812-821. DOI: 10.13336/j.1003-6520.hve.20220400
Citation: WU Min, JIANG Wei, LUO Yingting, SHEN Daoyi, YANG Junjie. Multi-source Partial Discharge Pattern Recognition in GIS Based on Improved SSD[J]. High Voltage Engineering, 2023, 49(2): 812-821. DOI: 10.13336/j.1003-6520.hve.20220400

基于改进SSD的GIS多源局放模式识别

Multi-source Partial Discharge Pattern Recognition in GIS Based on Improved SSD

  • 摘要: 为了克服局部放电(partial discharge, PD)缺陷诊断中样本数量不足的困难,并解决传统模式识别算法无法有效识别多源局放的缺陷,文中提出了一种基于改进单阶段多框预测算法(single shot multi-box detector,SSD)的气体绝缘组合电器(gas insulated switchgear, GIS)多源局放谱图检测算法。首先,分析了多源局放的相位分布局部放电(phase resolve partial discharge, PRPD)谱图特征,搭建GIS实验平台并模拟了4种典型局放缺陷,采集样本数据并采用ACGAN算法进行样本扩充。然后,搭建了SSD网络模型,在特征提取网络中引入了空间与通道注意力机制。最后,利用实验室数据与某220 kV变电站收集的现场数据分别验证所提出算法的有效性。实验结果表明,提出的算法能够有效检测出复杂噪声下PRPD谱图中的多源局放特征,其实验室数据平均检测精度可达97.8%,现场数据平均检测精度可达91.6%。

     

    Abstract: In order to overcome the difficulty of insufficient sample size in partial discharge (PD) defect diagnosis, and to solve the defect that multi-source PD cannot be effectively identified by traditional pattern recognition algorithms, an improved SSD (single shot multi-box detector)-based multi-source PD map detection algorithm for gas insulated switchgear (GIS) was proposed. Firstly, the PRPD (phase resolve partial discharge) spectral characteristics of multi-source partial discharge were analyzed, GIS experimental platform was built and four typical partial discharge defects were simulated, sample data were collected, and ACGAN was used for sample expansion. Then, an SSD network model was built, and a spatial and channel attention mechanism was introduced into the feature extraction network. Finally, laboratory data and field data collected from a 220 kV substation were used to verify the effectiveness of the proposed algorithm. The experimental results show that the proposed algorithm can be adopted to effectively detect the multi-source partial discharge features in the PRPD spectrum under complex noise. The average detection accuracy of laboratory data can reach 97.8%, and the average detection accuracy of field data can reach 91.6%.

     

/

返回文章
返回