马燕君, 谭令其, 马凯, 李歆蔚, 李盈. 半桥型MMC-HVDC子模块故障诊断与定位方法[J]. 高电压技术, 2022, 48(11): 4600-4609. DOI: 10.13336/j.1003-6520.hve.20220226
引用本文: 马燕君, 谭令其, 马凯, 李歆蔚, 李盈. 半桥型MMC-HVDC子模块故障诊断与定位方法[J]. 高电压技术, 2022, 48(11): 4600-4609. DOI: 10.13336/j.1003-6520.hve.20220226
MA Yanjun, TAN Lingqi, MA Kai, LI Xinwei, LI Ying. A Fault Detection and Location Method for Sub-module in Half-bridge MMC-HVDC Transmission System[J]. High Voltage Engineering, 2022, 48(11): 4600-4609. DOI: 10.13336/j.1003-6520.hve.20220226
Citation: MA Yanjun, TAN Lingqi, MA Kai, LI Xinwei, LI Ying. A Fault Detection and Location Method for Sub-module in Half-bridge MMC-HVDC Transmission System[J]. High Voltage Engineering, 2022, 48(11): 4600-4609. DOI: 10.13336/j.1003-6520.hve.20220226

半桥型MMC-HVDC子模块故障诊断与定位方法

A Fault Detection and Location Method for Sub-module in Half-bridge MMC-HVDC Transmission System

  • 摘要: 模块化多电平换流器(modular multilevel converter, MMC)是高压大容量柔直输电系统的核心设备,对其功率模块的故障诊断和快速隔离直接关系到模块内部故障范围,甚至是整个换流阀乃至系统的可靠运行能力。为了准确定位并快速隔离故障功率模块,基于半桥型MMC的子模块故障特性,提出一种半桥型MMC子模块故障诊断与定位方法。针对子模块故障引起的充放电电容数目与阀控系统投入子模块数目的差异,利用桥臂整体电压电流构造故障判据,实现桥臂内子模块器件IGBT开路及直通短路等故障的诊断,并通过各子模块的动态电气量差异定位故障子模块。基于PSCAD/EMTDC搭建了±400 kV的双端MMC-HVDC系统,对所提故障诊断和定位方法进行仿真验证,仿真结果表明,该方法具有快速诊断子模块故障类型和定位故障子模块的能力。

     

    Abstract: Modular multilevel converter (MMC) is a key device of voltage-source-converter based high-voltage-direct-circuit (VSC-HVDC) transmission system, the sub-module fault detection technology of which will directly influence the damage severity, even the reliability of the converter or the whole system. Aiming at fault diagnosis and isolation of sub-module, we analyzed the sub-module fault characteristics in half-bridge MMC-HVDC transmission system, based on which a fault detection and location method was proposed. By contrast of the actual value and the reference value of inserted sub-modules, the whole bridge voltage and current can be taken to construct the sub-module fault criterion for the diagnosis of faults such as open-circuit and direct short-circuit of sub-module IGBT, and then the dynamic change of sub-module voltage is further used to locate the faulty sub-module. A ±400 kV two-terminal MMC-HVDC transmission system based on PSCAD/EMTDC is built to conduct the simulated verification, and it is verified that the fault diagnosis and location method is effective.

     

/