350 MW热电联产机组深度调峰经济运行策略

Economic Operation Strategy for Deep Peak Regulation of a 350 MW Combined Heat and Power Unit

  • 摘要: 为了优化热电联产机组在不同深度调峰状态和电价时段下的运行策略,采用数理建模、深度耦合和智能优化等方法进行了研究。研究发现,在单机组运行过程中,当调峰考核金额较大时,适当增加售热量可平衡利润,避免节点负利润现象。不同调峰时期的利润差异显著:供暖期低负荷运行利润优于高负荷运行,非供暖期抢发电量可以获得更高收益。基于单机组研究,进一步进行负荷分配研究,发现相同工况下双机组运行的煤耗率大于单机组运行,但由于调峰补偿政策的支持,其利润远高于单机组运行。电价政策耦合研究显示,电价峰值期间机组高负荷运行可以显著提高收益,而在电价谷值期间应避免在调峰负荷节点附近运行,以防止严重亏损。研究结果为热电联产机组的优化调度提供了科学依据。

     

    Abstract: To optimize the operation strategy of combined heat and power unit under different deep peak regulation conditions and electricity price periods, methods such as mathematical modelling, deep coupling, and intelligent optimization were adopted for research. The study found that during single unit operation, when the peak regulation assessment price is higher, the heat-supply amount can be appropriately increased, so as to balance profits and avoid negative profit situations at certain nodes. Profits vary significantly under different peak regulation periods: the profit of low load operation is prior to that of high load operation during heat-supply period, while the priority dispatch of power generation can obtain higher profits during non heat-supply period. Further researches were conducted on load distribution based on single unit research. Results reveal that, the coal consumption rate of double units operation is higher than that of single unit operation under same operation conditions. However, due to the support from peak regulation compensation policies, the profit of double units operation is much higher than that of single unit operation. Researches on the coupling of electricity price policies show that, the profit can be significantly increased with the high load operation of the unit during peak electricity price period, while the unit should be avoided to operate near peak regulation load nodes during valley electricity price period, so as to prevent serious losses. Research findings can provide a scientific basis for optimizing the dispatch of combined heat and power units.

     

/