Analysis and application of a method to prevent the faulty action of the backup automatic switching of the light-load substation from being caused by the PT disconnection of the busbar[J]. 能源电力期刊集群平台, 2022, (0).
Citation: Analysis and application of a method to prevent the faulty action of the backup automatic switching of the light-load substation from being caused by the PT disconnection of the busbar[J]. 能源电力期刊集群平台, 2022, (0).

Analysis and application of a method to prevent the faulty action of the backup automatic switching of the light-load substation from being caused by the PT disconnection of the busbar

  • When the power backup automatic switching device of the power station is in the state of charging and light load, if the bus PT is disconnected at this time, the backup automatic switching device will malfunction because the current does not meet the threshold value, resulting in the action of backup automatic switching in normal operation state. This paper analyzes the principle of countermeasures to prevent the malfunction of the substation under the condition of light load, and proposes a more optimized solution based on the example of the transformation of a substation, in order to find a solution that can be popularized and applied to prevent the backup under light load. A method of malfunctioning under operating conditions.