The outer-loop control is often ignored when using impedance method to solve the stability problem of the grid-connected doubly fed induction generator (DFIG) system. However
the influence of ignoring the outer-loop control on the stability of the system has not been deeply studied. To solve this problem
firstly
this paper proposes a broadband frequency admittance model of DFIG which includes both stator- rotor side converter (RSC) and grid side converter (GSC) with integrated power outer-loop controls. The accuracy and validity of the proposed admittance model are verified by electromagnetic transient simulation model. Secondly
based on the actual operational parameter ranges provided by wind turbine manufacturer
influence of variations in outer-loop control parameters on the admittance characteristics of DFIG is analyzed theoretically. The results demonstrate that variations in proportional coefficients significantly affect the admittance characteristics of DFIG. Further studies indicate that overlooking RSC outer-loop control may hinder the recognition of oscillation problems when using the impedance method in the grid-connected DFIG system across various frequency bands. This may lead to erroneous assessment of an actually oscillatory system as stable system
thereby posing a risk to the safe operation of the power system. Next
a practical example of grid-connected DFIG wind farm is established
and the impact of RSC outer-loop control parameters on oscillation stability is observed by the variation of RSC outer-loop control parameters
which validates the crucial role of incorporating the power outer-loop when impedance analysis is applied for oscillation stability assessment of grid-connected DFIG system.
CHI Y N, TANG B J, HU J B, et al.Overview of mechanism and mitigation measures on multi-frequency oscillation caused by large-scale integration of wind power[J]. CSEE journal of power and energy systems, 2019, 5(4): 433-443.
FAN L L, MIAO Z X.Nyquist-stability-criterion-based SSR explanation for type-3 wind generators[J]. IEEE transactions on energy conversion, 2012, 27(3): 807-809.
MIAO Z X.Impedance-model-based SSR analysis for type 3 wind generator and series-compensated network[J]. IEEE transactions on energy conversion, 2012, 27(4): 984-991.
SONG Y P, WANG X F, BLAABJERG F.Impedance-based high-frequency resonance analysis of DFIG system in weak grids[J]. IEEE transactions on power electronics, 2017, 32(5): 3536-3548.
PANG B, NIAN H, XU Y Y.Mechanism analysis and damping method for high frequency resonance between VSC-HVDC and the wind farm[J]. IEEE transactions on energy conversion, 2021, 36(2): 984-994.
WANG X F, HARNEFORS L, BLAABJERG F.Unified impedance model of grid-connected voltage-source converters[J]. IEEE transactions on power electronics, 2018, 33(2): 1775-1787.
WEN B, BOROYEVICH D, BURGOS R, et al.Analysis of D-Q small-signal impedance of grid-tied inverters[J]. IEEE transactions on power electronics, 2016, 31(1): 675-687.
SUN K, YAO W, FANG J K, et al.Impedance modeling and stability analysis of grid-connected DFIG-based wind farm with a VSC-HVDC[J]. IEEE journal of emerging and selected topics in power electronics, 2020, 8(2): 1375-1390.
CHEN X J, LIU Z G.Impedance modeling and stability analysis of the converters in a double-fed induction generator (DFIG)-based system[J]. Energies, 2019, 12(13): 2500.
WEN B, DONG D, BOROYEVICH D, et al.Impedance-based analysis of grid-synchronization stability for three-phase paralleled converters[J]. IEEE transactions on power electronics, 2016, 31(1): 26-38.