Cause analysis and treatment of transverse differential protection device action for a hydraulic generator
摘要
针对一起水轮发电机横差保护动作故障进行分析
找出故障原因
提出改进措施。分析结果表明:由于7号、8号磁极间连片烧断
导致绕组发生匝间短路
引起横差保护动作;更换7号、8号磁极后
机组运行正常
再未发生横差保护动作现象。
Abstract
Aiming at the failure of transverse differential protection device action of a hydraulic gen?erator
checks and analyzes the reasons
brings forward the improvement measures. The analysis resultshows that owing to the connector between No.7 and No.8 magnetic pole burns out
brings on interturnshort circuit of the winding
aroses transverse differential protection device action. After chengingNo.7 and No.8 magnetic pole
the unit operates normally
and transverse differential protection deviceaction never happened again.