摘要
针对 WBT-822A 型备自投保护与 RCS-941 型线路保护二次回路配合上存在的问题
根据《10 kV-110(66)kV线路保护及辅助装置标准化设计规范》进行深入分析
提出了有效的解决方案。结果表明:在进线保护操作箱回路增加一个重动继电器
可消除备自投误动或拒动的安全隐患
为电网的安全稳定运行提供了保障。
Abstract
Aiming at the problems of secondary loop coordination between the type of WBT-822Astandby power auto-switching in protecting device and the type of RCS-941 line protection device
ac?cording to ’Standardzation design criterion for 10 kV-110(66) kV transmiting lines protection and as?sistant equipment ’makes deep analysis