徐彪, 李辉, 谭力铭, et al. Analysis of Causes and Countermeasures for Maloperation of Distance Protection on Wind Farm Transmission Lines[J]. 2025, 45(6): 107-113.
徐彪, 李辉, 谭力铭, et al. Analysis of Causes and Countermeasures for Maloperation of Distance Protection on Wind Farm Transmission Lines[J]. 2025, 45(6): 107-113. DOI: 10.3969/j.issn.1008-0198.2025.06.014.
Analysis of Causes and Countermeasures for Maloperation of Distance Protection on Wind Farm Transmission Lines
Starting from an on-site misoperation accident of the distance protection for a wind farm transmission line
this paper analyzes the causes of such misoperation from the perspective of criterion mechanism
and conducts a comparative analysis on the special protection behaviors under this fault scenario. On this basis
performance tests and criterion comparisons on the distance protection devices of mainstream relay protection manufacturers are further carried out through methods such as on-site fault recording playback and RTDS simulation tests. The analysis reveals the mechanism by which the wind farm transmission lines affect the distance protection
and finally corresponding strategies are formulated at the level of protection criteria in combination with on-site realities.
WANG T,SONG G,HUSSAIN K S T. Three-phase adaptive auto-reclosing for single outgoing line of wind farm based on active detection from STATCOM[J]. IEEE Transactions on Power Delivery,2020,35(4):1918-1927.
JOLHE S P,DHOMANE G A,KARALKAR M D.Design of protection and control scheme for hybrid nanogrid[J]. Protection and Control of Modern Power Systems,2022,46(10):33-42.
XU X,YAN Z,SHAHIDEHPOUR M,et al.Power system voltage stability evaluation considering renewable energy with correlated variabilities[J]. IEEE Transactions on Power Systems,2018,33(3):3236-3245.