LI Shengqing, TANG Xinyun, ZHU Hui, et al. Harmonic Mixed Damping Control Strategy for LLCL Grid-Connected Inverter in Weak Power Grid[J]. 2022, 42(6): 54-58.
LI Shengqing, TANG Xinyun, ZHU Hui, et al. Harmonic Mixed Damping Control Strategy for LLCL Grid-Connected Inverter in Weak Power Grid[J]. 2022, 42(6): 54-58. DOI: 10.3969/j.issn.1008-0198.2022.06.009.
Harmonic Mixed Damping Control Strategy for LLCL Grid-Connected Inverter in Weak Power Grid
In order to suppress the harmonics of switching frequency and system resonant peak in weak power grid
a harmonic mixed damping control strategy for LLCL grid-connected inverter in weak power grid is proposed.First the LLCL type and LCL type amplitude frequency characteristics of the filter are analyzed
and then based on the active damping method to add the passive damping method
through the active damping of k value and R value set in the passive damping
under the condition of no more loss
the effect of active damping method by control delay is reduced
combining the advantages of two methods.Finally
the simulation results show that the proposed control strategy has good harmonic suppression effect
and the total harmonic distortion rate is reduced by 1.18% compared with the active damping method
and it has good stability and adaptability under different weak power networks.
Han Y, Li Z, Yang P, et al. Analysis and design ofimproved weighted average current control strategy for LCL-type grid-connected inverters[J]. IEEE Transactions on Energy Conversion, 2017, 32(3): 941-952.
Zhu Jiaxiong, Xiao Zhigang, Feng Chang. Simulation of LLCL filter based on active damping weighted current control strategy[J]. MATEC Web of Conferences, 2021, 336(01011):1-6.