Tang Xiong-min, Du Fang-zhou, Chen Si-zhe. Research on a New Implementation Method for Single-Phase Shunt Active Power Filter[J]. 2016, 33(3): 11-18.DOI: 10.3969/j.issn.1007-7162.2016.03.003.
Research on a New Implementation Method for Single-Phase Shunt Active Power Filter
A new implementation method for single-phase shunt active power filter (APF) with single closed-loop control strategy is presented. The ideal compensation current instruction is deduced with single PQ theory
which applies with actual and virtual quartered single-phase current and voltage. Based on the ideal compensation current
the practical compensation current instruction is achieved with power predictive algorithm. Because the power predictive algorithm is adopted
the single closed-loop control strategy can be used in APF application. There is no voltage control loop in the implementation method
so the method has many favorable characteristics
such as easy designing
fast responding
strong robustness
etc. The different conditions of APF
such as startup
normal operation and load change
are also researched in the paper. The validity of implementation method for APF is proved by simulation and experimental results.