DENG Xiangli, LIU Meihan, ZENG Ping, et al. 基于漏磁场相位变化特征的变压器绕组早期故障保护研究[J]. Power System Protection and Control, 2025, (24).
DOI:
DENG Xiangli, LIU Meihan, ZENG Ping, et al. 基于漏磁场相位变化特征的变压器绕组早期故障保护研究[J]. Power System Protection and Control, 2025, (24). DOI: 10.19783/j.cnki.pspc.250109.
To address the difficulty of traditional transformer protection in effectively identifying early-stage faults such as minor inter-turn short circuits in transformer windings
this paper proposes an early fault protection scheme for transformer windings based on the phase change characteristics of the leakage magnetic field. First
an analytical model of the leakage magnetic field for a transformer with a non-ideal winding structure is established
and the variation of magnetic leakage distribution before and after winding failures is analyzed. Then
by combining the fault components such as magnetic leakage phase mutation
phase differences among multiple measuring points
and leakage amplitude ratio
a leakage phase differential protection criterion and a fault location logic are proposed
effectively avoiding the influence of temperature on the optical fiber measurement system. The leakage magnetic field analytical model is also used for setting the operating thresholds of the protection scheme. Finally
the feasibility and effectiveness of the proposed early fault identification and location scheme are verified by dynamic model experiments and finite element simulations.