WANG Yanting, FAN Shunyue, LIU Le, et al. 基于频域能量比值的柔性直流输电线路单端量高可靠性保护方案[J]. Power System Protection and Control, 2025, (20).
DOI:
WANG Yanting, FAN Shunyue, LIU Le, et al. 基于频域能量比值的柔性直流输电线路单端量高可靠性保护方案[J]. Power System Protection and Control, 2025, (20). DOI: 10.19783/j.cnki.pspc.241714.
To address the lack of effective setting criteria for frequency-domain protection of flexible DC transmission lines and to mitigate the protection maloperation issue due to lightning interference
this paper proposes a high-reliability non-unit protection based on frequency-domain energy ratio. First
this paper analyzes the frequency-domain expressions of line-mode voltage traveling waves under four typical conditions in flexible DC transmission systems: internal ground faults
external ground faults
line lightning interference
and lightning faults
revealing their frequency-domain distribution characteristics. Based on this
an energy operator is introduced to weight the voltage backward traveling wave amplitude-frequency curve
enhancing the discrimination of high-frequency components. Then
the energy accumulation ratio across different frequency bands is used to establish a criterion for identifying internal and external faults. Additionally
considering the significant differences in energy distribution in the low-frequency range due to lightning interference
an efficient method for lightning interference identification is proposed. Finally
a complete non-unit protection criterion for DC transmission lines is developed
supported by clear theoretical setting principles. Extensive simulation results validate that the proposed protection can quickly and reliably identify line faults while accurately detecting lightning interference
exhibiting strong tolerance to transition resistance and excellent anti-interference capability.