Flexible loop closing using single-core asymmetric phase shifting transformer (SAPST) can improve the success rate of traditional distribution network loop closures. However
the complex structure and intrinsic characteristics of SAPST increase the complexity of configuring protection devices
which may lead to malfunction or failure of protection actions and reduce protection sensitivity. To address these issues
an adaptive current protection method for loop closing networks employing SAPST is proposed. First
an equivalent model of the loop closing network containing SAPST is established
and the mechanism by which SAPST affects traditional current protection is analyzed. Then
based on the SAPST tap position information
a stage-I protection scheme is developed by calculating the short-circuit current using the fault compound sequence component relationships. A stage-II protection scheme is established by adjusting the branch coefficients. Additionally
switching criteria for protection schemes are designed to evaluate the loop closing status in real-time
and a flowchart for the loop closing protection scheme is proposed. Finally
the proposed protection scheme is verified using PSCAD/EMTDC and the RTlab hardware-in-the-loop simulation platforms. Experimental results demonstrate that the proposed scheme offers high selectivity and reliability
providing theoretical support for the engineering application of SAPST.