MA Junpeng, LI Lei, CHI Chengbin, et al. 宽短路比工况下构网型逆变器功率自同步控制的稳定性分析[J]. Power system protection and control, 2025, 45(7): 165-173.
DOI:
MA Junpeng, LI Lei, CHI Chengbin, et al. 宽短路比工况下构网型逆变器功率自同步控制的稳定性分析[J]. Power system protection and control, 2025, 45(7): 165-173. DOI: 10.19783/j.cnki.pspc.240664.
VSC)通过模拟同步机功角特性以实现电网支撑,但其在宽短路比(short-circuit ratio
SCR)运行工况下存在振荡风险。为分析构网型逆变器在宽短路比工况下的稳定情况,首先建立了PSC-VSC小信号模型,得到了有功、无功功率的传递函数,并以此揭示了GFM逆变器在宽短路比工况下小干扰失稳机理。结果表明,PSC-VSC在强电网下面临小信号失稳风险。进而提出基于功率自同步控制(power self-synchronization control
Grid forming (GFM) voltage source converters (VSC) based on the power synchronization control (PSC) are used to support the grid by emulating the power angle characteristics of synchronous machines. However
they face oscillation risks under wide range of short-circuit ratio (SCR) conditions. To analyze the stability of GFM converters under wide range SCR conditions
this paper establishes a small-signal PSC-VSC model
and the transfer functions of active and reactive power are derived. Based on this
the small-signal instability mechanism of GFM converters under wide range of SCR conditions is revealed. The results show that PSC-VSC faces small-signal instability risks in strong grid conditions. Subsequently
by limiting the gain of the active power transfer function
the power self-synchronization control (PSSC) based VSC control strategy is proposed to enhance the stability of GFM converters in strong grid conditions. Furthermore
the stability of PSSC-based GFM converters under grid faults is analyzed. Finally
the correctness and effectiveness of the proposed analysis method are verified through hardware-in-the-loop real-time simulation.