Subsynchronous Oscillation Characteristics Analysis of PMSG-based Wind Farms through LCC-HVDC Transmission System
摘要
“双碳”目标驱动新能源快速发展,大规模风电经由传统高压直流输电(Line-Commutated Converter Based HVDC
LCC-HVDC)并网外送是风电开发利用的主要方式,直驱风机与LCC-HVDC之间的交互作用不当是导致次同步振荡的主要原因,但其振荡机理和影响因素不明确。文中面向直驱风电场经LCC-HVDC外送系统的次同步振荡问题,通过扰动测辨法构建直驱风电场、直流输电系统和公共并网点(Point of Common Coupling
The "dual carbon"goal propels the quick growth of new energy
and the large-scale wind power is connected to the grid via the traditional high-voltage direct current transmission (LCC-HVDC),which is the main way of wind power development and utilization.Subsynchronous oscillation is mostly caused by an inappropriate interaction between direct drive wind farms and LCC-HVDC
however there are many different causes that might cause it.In this article
the sub-synchronous oscillation problem of direct-drive wind farm via LCC-HVDC transmission system is addressed
and the impedance model of direct-drive wind turbine
DC transmission system and Point of Common Coupling (PCC)port is constructed by perturbation determination method.Based on the impedance analysis method
a stability criterion applicable to the AC/DC system is proposed to analyze the dominant factors affecting the stability domain of the system and the influence of each device on the impedance characteristics of the system
and the influence law of the control parameters on the impedance characteristics of the system is revealed.The results show that a decrease in the proportional coefficient and an increase in the integral coefficient of the rectifier side controllers of the direct drive wind farm GSC and LCC-HVDC will lead to negative resistance characteristics in the impedance of LCC-HVDC and wind turbine ports
resulting in negative damping characteristics in the parallel impedance composed of the direct drive wind farm and LCC-HVDC
indicating the risk of sub synchronous oscillation in the system.Finally
the time domain simulation of PSCAD/EMTDC platform is carried out to further verify the influence of control parameters on system stability.