[1]李展洋,周维博,汪丽娜,等.电站间接空冷散热器冬季防冻临界运行参数研究[J].热力发电,2026,55(04):127-139.
[1]李展洋,周维博,汪丽娜,等.电站间接空冷散热器冬季防冻临界运行参数研究[J].热力发电,2026,55(04):127-139. DOI: 10.19666/j.rlfd.202507131.
DOI:10.19666/j.rlfd.202507131.
在冬季低温条件下,空冷散热器翅片管束易发生冻结。探究不同风速和风向条件下间接空冷系统临界防冻环境温度与临界防冻循环水流量的变化规律,对保障电厂安全稳定运行具有重要指导意义。以某2×350 MW间接空冷机组为研究对象,采用数值模拟方法,结合百叶窗开度调节策略,对不同工况下间接空冷系统的临界防冻特性进行研究。通过对冬季不同环境气象条件下间接空冷系统流动传热性能变化规律进行分析计算,揭示了不同风速、风向以及不同百叶窗开度条件下间接空冷系统临界防冻环境温度和临界防冻流量变化规律。结果表明:环境风速升高导致临界防冻环境温度降低、临界防冻流量增大;通过降低百叶窗开度可以降低临界防冻环境温度,而临界防冻流量呈先降后升的变化趋势,但在270°风向高风速条件下,临界防冻流量随百叶窗开度减小而持续降低。研究结论可为间接空冷机组在冬季低温环境下安全稳定运行提供运行指导。
Under low-temperature conditions in winter
the fin-tube bundles of air-cooled radiators are prone to freezing. Exploring the variation patterns of the critical anti-freezing ambient temperature and critical anti-freezing circulating water flow rate of the indirect air-cooling system at different wind speeds and directions is of great guiding significance for ensuring the safe and stable operation of power plants. Taking a 2×350 MW indirect aircooled unit as the research object
this study adopts the numerical simulation method
combining with the louver opening adjustment strategy
to investigate the critical anti-freezing characteristics of the indirect air-cooling system under different operating conditions. Through the analysis and calculation of the variation patterns of the flow and heat transfer performance of the indirect air-cooling system under different ambient meteorological conditions in winter
the variation laws of the critical anti-freezing ambient temperature and critical anti-freezing flow rate of the indirect air-cooling system at different wind speeds
wind directions and louver openings are revealed. The results show that an increase in ambient wind speed leads to a decrease in the critical anti-freezing ambient temperature and an increase in the critical anti-freezing flow rate. Reducing the louver opening can lower the critical antifreezing ambient temperature
while the critical anti-freezing flow rate shows a trend of decreasing at first and then increasing. However
under the condition of high wind speed in the 270° wind direction
the critical anti-freezing flow rate decreases continuously with the reduction of louver opening. The research conclusions can provide operational guidance for the safe and stable operation of indirect air-cooled units in low-temperature winter environments.
卜永东,杨立军,杜小泽,等.电站空冷技术[J].现代电力, 2013, 30(3):69-79.BU Yongdong, YANG Lijun, DU Xiaoze, et al. Review of dry cooling technologies in power plants[J]. Modern Electric Power, 2013, 30(3):69-79.
CHEN L, YANG L J, DU X Z, et al. Anti-freezing of aircooled heat exchanger by air flow control of louvers in power plants[J]. Applied Thermal Engineering, 2016,106:537-550.
孟令国,杨芳,陈承宪,等.严寒地区间接空冷塔防冻措施研究[J].电力勘测设计, 2021(增刊1):13-18.MENG Lingguo, YANG Fang, CHEN Chengxian, et al.Research on antifreeze of indirect dry cooling tower in severe cold region[J]. Electric Power Survey&Design,2021(Suppl.1):13-18.
顾红芳,王海军,陈琦,等.百叶窗开度对间接空气冷却塔冬季防冻的影响[J].热力发电, 2016, 45(4):70-75.GU Hongfang, WANG Haijun, CHEN Qi, et al. Effect of louver opening degree on anti-freezing performance of natural drafted air-cooling tower[J]. Thermal Power Generation, 2016, 45(4):70-75.
WEI H M, GE Z H, YANG L J, et al. Entransy based optimal adjustment of louvers for anti-freezing of natural draft dry cooling system[J]. International Journal of Heat and Mass Transfer, 2019, 134:468-481.
康卫东,李高潮,王子豪,等.基于环境风温-冷却水温耦合计算的间接空冷塔冬季运行及防冻研究[J].华东理工大学学报(自然科学版), 2023, 49(4):474-480.KANG Weidong, LI Gaochao, WANG Zihao, et al. Winter operation and anti-freezing research of indirect air-cooling tower based on coupling calculation between ambient wind temperature and cooling water temperature[J].Journal of East China University of Science and Technology(Natural Science Edition), 2023, 49(4):474-480.
赵倩.气侧流场优化对冷却三角两侧管束传热特性及水温分布的影响机制[D].济南:山东大学, 2024:1.ZHAO Qian. Effect mechanism of the aerodynamic field optimization on cooling triangle bilateral bundles heat transfer characteristics and water temperature distribution[D]. Jinan:Shandong University, 2024:1.
WANG W J, YANG L J, DU X Z, et al. Anti-freezing water flow rates of various sectors for natural draft dry cooling system under wind conditions[J]. International Journal of Heat and Mass Transfer, 2016, 102:186-200.
李文东.自然通风间接空冷塔关键参数分布特性及其影响机理[D].济南:山东大学, 2020:1.LI Wendong. Distribution characteristics and effect mechanism of key parameters for natural draft dry cooling tower[D]. Jinan:Shandong University, 2020:1.
王伟佳,陈磊,孔艳强,等.电站间接空冷系统防冻高效运行控制逻辑及数值验证[J].中国电机工程学报,2022, 42(6):2258-2268.WANG Weijia, CHEN Lei, KONG Yanqiang, et al. Antifreezing controlling logics and numerical verification for natural draft dry cooling system in power plant[J].Proceedings of the CSEE, 2022, 42(6):2258-2268.
岳金鸿.间接空冷系统散热器传热及防冻性能的研究[D].北京:华北电力大学, 2023:1.YUE Jinhong. Research on heat transfer and antifreezing performance of radiator in indirect air cooling system[D].Beijing:North China Electric Power University, 2023:1.
WANG W J, KONG Y Q, WANG F L, et al. Anti-freezing prediction model for different flow patterns of air-cooled heat exchanger[J]. International Journal of Heat and Mass Transfer, 2020, 153:119656.
张明玉,王晓静,关欣,等.间接空冷翅片管束临界防冻特性及防冻裕量研究[J].热力发电, 2024, 53(4):92-101.ZHANG Mingyu, WANG Xiaojing, GUAN Xin, et al.Anti-freezing characteristics and margin of indirect aircooled finned tube bundle[J]. Thermal Power Generation,2024, 53(4):92-101.
ZHANG W W, MA L, JIA B, et al. Optimization of the circulating cooling water mass flow in indirect dry cooling system of thermal power unit using artificial neural network based on genetic algorithm[J]. Applied Thermal Engineering, 2023, 223:120040.
王晗昀.大型火电机组间接空冷塔防冻策略研究[D].南京:东南大学, 2017:1.WANG Hanyun. Study on anti-freezing strategy for indirect air-cooling tower of large capacity fossil-fired generating unit[D]. Nanjing:Southeast University,2017:1.
YANG X R, WEI H M, JIN R N, et al. Anti-freezing of air-cooled heat exchanger with rolling-type windbreaker[J]. International Journal of Heat and Mass Transfer, 2019, 136:70-86.
ZHOU J X, MA H, SI F Q, et al. To broaden safe operation range of the indirect dry cooling system with internal annular windbreak cloth in extremely cold days[J].Applied Thermal Engineering, 2019, 152:420-429.
MA H, SI F Q, ZHU K P, et al. Utilization of partial through-flow tower shell to cope with the excess cooling capacity of dry cooling tower in extremely cold days with crosswind[J]. International Journal of Thermal Sciences,2019, 136:70-85.
WANG W J, CHEN L, KONG Y Q, et al. Cooling performance evaluation for double-layer configuration of air-cooled heat exchanger[J]. International Journal of Heat and Mass Transfer, 2020, 151:119396.
YANG L J, WU X P, DU X Z, et al. Dimensional characteristics of wind effects on the performance of indirect dry cooling system with vertically arranged heat exchanger bundles[J]. International Journal of Heat and Mass Transfer, 2013, 67:853-866.
0