CHEN Ou, TENG Da, LU Guangjie, et al. Characteristics analysis for centralized heating system using saturated flue gas waste heat in coal-fired power plants[J]. Thermal power generation, 2024, 53(12): 102-111.
DOI:
CHEN Ou, TENG Da, LU Guangjie, et al. Characteristics analysis for centralized heating system using saturated flue gas waste heat in coal-fired power plants[J]. Thermal power generation, 2024, 53(12): 102-111. DOI: 10.19666/j.rlfd.202405101.
Characteristics analysis for centralized heating system using saturated flue gas waste heat in coal-fired power plants
Direct discharging of saturated flue gas from coal-fired utility boiler can lead to significant low-grade waste heat loss. The saturated flue gas waste heat recovery and utilization for centralized heating system is constructed
the operating parameters of the heating system in coal-fired power plant are analyzed
and the feasibility that the saturated flue gas waste heat can be used to heat the return water of the heating system is verified. Finally
the economic efficiency of the centralized heating system is investigated for operation with different targets
and the influence characteristics of the operating parameters are revealed for the thermal performance of the centralized heating system. The research results show that
the temperature of flue gas waste heat can be increased by 30~40 ℃ by absorption heat pump. With the 350 MW coal-fired heating unit as an example
the absorption heat pump recovers the saturated flue gas waste heat with 50.23 MW for re-utilization.The economic benefits brought by enhancing the heating capacity are significantly better than those corresponding to the increase in power generation
and the heating capacity of the coal-fired power plant is increased by 13.4%
and the annual heating revenue is increased by 19 752 000~34 423 200 yuan. The research provides technical references for the saturated flue gas waste heat recovery and utilization in coal-fired power plants.