MENG Long, ZHANG Weike, LI Junwan, et al. On-line locating technology for condenser cooling tube leakage in power plant[J]. Thermal power generation, 2025, 54(1): 162-170.
DOI:
MENG Long, ZHANG Weike, LI Junwan, et al. On-line locating technology for condenser cooling tube leakage in power plant[J]. Thermal power generation, 2025, 54(1): 162-170. DOI: 10.19666/j.rlfd.202405098.
On-line locating technology for condenser cooling tube leakage in power plant
To improve timeliness and accuracy of the location of condenser leakage cooling tube and solve the problem that the leakage cooling tube cannot be located online
the optimal route of leakage cooling tube location technology is demonstrated by combining theoretical analysis with experimental research. The results show that the tracer gas leakage detection technology has the characteristics of high positioning efficiency and high positioning accuracy
and is suitable for developing on-line locating technology of condenser leakage cooling tube. Through establishing the relationship model between and among the helium concentration change value
time
and water tank liquid level during the isolation of one half of the condenser for draining water
the height of the condenser leakage cooling tube can be located
so as to determine the condenser leakage tube row.