Run-test and simulation research of a beam-down concentrating solar power plant
The beam-down concentrating solar power plant has the advantages of high concentrating ratio
low installation and maintenance requirements
and low pump consumption. Relying on the 50 MW beam-down tower concentrating solar power station in Yumen Xinneng First Power Co.
Ltd.
the mathematical models of the heliostat field
hyperboloid mirror
receiver
molten salt tank
and power generation cycle are established and verified. The run-test results reveal that
the maximum outlet temperature of the molten salt can be maintained at 559 ℃ for 50 minutes at an average direct normal irradiation of 739.70 W/m~2. The cosine efficiency
shading and blocking efficiency
shading efficiency of the hyperboloid mirror
and attenuation efficiency of the heliostat field at 12:00 are 0.856 8
0.999 7
0.994 1
and 0.974 6
respectively. The average hyperboloid mirror flux density and receiver flux density are 11.3 kW/m~2 and 400.5 kW/m~2
respectively. Meanwhile
the power station is maintained for 16 h at the rated generation power of 50 MW. The research has certain reference significance for the operation of a beam-down concentrating solar power plant.