Anti-freezing characteristics and margin of indirect air-cooled finned tube bundle
The anti-freezing operation parameters of indirect air-cooled finned bundle are insufficient at present.To solve this problem
this research firstly concludes the anti-freezing model of finned tube bundle
including the thermal equilibration equations
water side and air side transport equations
as well as anti-freezing constrains.Secondly
based on the co-current and counter-current air-cooled finned tube bundles
the critical anti-freezing characteristics and margin are analyzed. Then
the critical values are discovered for finned tube bundles with middle inlet
left inlet and side inlet patterns. The research shows that
as the ambient temperature or inlet water temperature reduces
as well as the ambient wind increases
the critical anti-freezing water flow rate ascends.Besides
when the inlet water temperature decreases
the wind effects get intensified. The anti-freezing performance of counter-current finned tube bundle is inferior to that of the co-current type
meanwhile the difference becomes expanded if the wind increases or water inlet temperature decreases. The effects of inlet water temperature elevation on anti-freezing margin can be classified into three levels
which are termed as obvious range(0 ℃
10 ℃]
slow range(10 ℃
20 ℃]
and stable range(20 ℃
40 ℃]. Therefore
power plants should not always increase the water flow rate for anti-freezing operation. The air-cooled finned tube bundle with middle inlet pattern has better anti-freezing performance than others
so it's suggested preferentially for coal-fired or nuclear power plants. This research may provide guidelines of anti-freezing operation for dry-cooling power stations in China.