Feasibility analysis of peak shaving for coal-fired units based on molten salt heat storage
With the continuous increase of installed capacity of new energy generation in power grid
thermal power units have to undertake more peak shaving. However
the flexibility and peak shaving capacity of current thermal power units are generally insufficient. A subcritical 300 MW coal-fired unit is retrofitted for molten salt energy storage. Six heat storage strategies and two heat release strategies are proposed and investigated. The influence of heat storage and release process on the peak shaving capacity and thermal performance of the unit under three working conditions is analyzed
the technical and economic analysis is performed in terms of the net present value.The results show the feasibility of extracting reheated steam for heat storage is higher
with a peak shaving depth of 58.9%. However
the coal consumption would increase at the same time. During the releasing heat stage
the maximum increment of power generation up to 11.3% of the rated power generation is achieved by heating the water supply to generate steam
while the higher temperature of the molten salt is required. Using high-temperature molten salt instead of low-pressure heater to preheat water supply is proved to have more advantages
while the power generation increment is relatively small. During the whole process of heat storage and release
the maximum circulating electricity efficiency can reach 0.987. The economic analysis of heat storage transformation is conducted.The dynamic investment payback period is 11.65 years
and the net present value is 49.118 million yuan. Therefore
Configuration analysis of coupled molten salt heat storage system for 1 000 MW coal-fired unit
CORRELATION BETWEEN TEST COEFFICIENTS OF INDUSTRIAL COOLING TOWER AND SIMULATED TESTING TOWER
MEASUREMENT AND CALCULATION METHOD FOR THERMAL PERFORMANCE TEST OF ULTRA-SUPERCRITICAL UNIT WITH STEAM TURBINE EQUIPPED WITH DOUBLE-ROW HIGH-PRESSURE HEATERS
Performance study on water drenching filler with modified small spacing in cooling towers
Thermal performance analysis on geothermal-solar power generation system
Related Author
CHEN Xun
CHEN Zhengqi
ZHOU Ke
SHENG Kai
ZHU Guangming
LIU Ming
HU Sanji
CHEN Yuling
Related Institution
State Grid Hunan Electric Power Co., Ltd. Electric Power Science Research Institute
School of Energy and Power Engineering, Xi'an Jiaotong University
Department of Power Engineering, North China Electric Power University
Xi'an Thermal Power Research Institute Co., Ltd
Hunan Xiangdian Experimental Research Institute Co., Ltd