LI Xianfeng, HU Chengang, GAO Zhenyu, et al. Evaluation method of contact state of GIS disconnector based on multi-feature fusion[J]. Thermal power generation, 2023, 52(5): 22-28.
DOI:
LI Xianfeng, HU Chengang, GAO Zhenyu, et al. Evaluation method of contact state of GIS disconnector based on multi-feature fusion[J]. Thermal power generation, 2023, 52(5): 22-28. DOI: 10.19666/j.rlfd.202208205.
Evaluation method of contact state of GIS disconnector based on multi-feature fusion
The existing GIS disconnector contact state evaluation method is based on the single state characteristic quantity
the reliability of the evaluation result is low
and it is easy to misjudge and erroneous judgment. So a method of GIS disconnector contact state evaluation based on multi-feature fusion was presented. The multi state quantity comprehensive detection experimental platform of 220 k V GIS disconnector was built. And the relationships between the GIS disconnector shell temperature signal
shell vibration signal
partial discharge signal and the contact state of the disconnector were experimentally studied. On this basis
the temperature rise of GIS disconnector shell
the amplitude of shell vibration signal and the discharge amplitude of partial discharge UHF signal were taken as the state characteristic quantities of disconnector
and the contact state evaluation model of disconnector based on support vector machine was established. The test results show that the accuracy of GIS disconnector contact state evaluation method based on multi-feature fusion is the highest