Study on coupling scheme of liquid compressed carbon dioxide energy storage system and thermal power unit
Flexible transformation of thermal power units is the key to build a new power system and achieve the goal of “carbon peak” and “carbon neutrality”. In order to promote the flexibility of thermal power units
the coupling scheme for small steam turbine drive and motor drive liquid compressed carbon dioxide energy storage system and thermal power unit is put forward
and the thermodynamic system model is established. Moreover
the heat consumption rate and energy utilization coefficient are used to evaluate the system
the thermodynamic performance of the system is compared and analyzed
and the optimal coupling scheme of energy storage is established. The researches show that
in the energy storage stage
condensate water is extracted from the outlet of the condensate pump
and the compressed heat is absorbed and returned to the outlet of No.7 low-pressure heater. In the energy release stage
steam is extracted from the exhaust of the middle pressure cylinder
and the expanded CO_2 is heated and returned to the No.5 low-added hydrophobic cooler
the coupling system has the best performance. The heat consumption rate is 48.308 k J/(k W·h) lower than that of the original system
and the energy utilization coefficient increases by 0.52 percentage point. Changing the inlet temperature and the mass flow rate of CO_2 expander can quickly change the load. After coupling with the energy storage system
the peak regulation capacity of thermal power unit increases by 17.1%
when the hot water tank is configured and the maximum heat is released
the peak regulation capacity of the unit increases by 37.4%
indicating the flexibility of thermal power unit is improved.