Effect of air guiding baffles on performance of natural draft wet cooling tower
The thermal performance of natural draft counterflow wet cooling towers is greatly affected by ambient cross wind
this situation can be improved by applying air guiding baffles at air inlet of the tower. To test the effect of air guiding baffles
this paper studies a 1 000 MW power generation unit with a 13 000 m~2 natural draft counter-flow wet cooling tower located at strong wind region. Through field tests under the same operating and ambient conditions
the effects of adding air guiding baffles on basin water temperature and thermal performance of the cooling tower are studied. The results show that
the adverse effect of ambient cross wind on natural draft counter-flow wet cooling towers can be effectively reduced by applying air guiding baffles. Under the same operating and ambient conditions
the basin water temperature of the cooling tower with air guiding baffles is lower than that of the same type cooling tower without the air guiding baffles. Within the test range
this basin water temperature difference becomes more significant with the increasing ambient wind speed. When the wind speed v is below 3 m/s
the basin water temperature is basically the same. When 3 m/s≤v5 m/s
the viariation range of basin water temperature is 0.24~0.61 ℃. When 5 m/s≤v8 m/s
the variation range of the basin water temperature is 0.71~0.97 ℃.
HYDRAULIC COMPUTATION FOR WATER DISTRIBUTION SYSTEM COMBINED WITH CHANNEL TUBES IN CENTRAL SHAFT OF COUNTERFLOW TYPE NATURAL COOLING TOWER AND VERIFICATION THEREOF
CORRELATION BETWEEN TEST COEFFICIENTS OF INDUSTRIAL COOLING TOWER AND SIMULATED TESTING TOWER
MEASUREMENT AND CALCULATION METHOD FOR THERMAL PERFORMANCE TEST OF ULTRA-SUPERCRITICAL UNIT WITH STEAM TURBINE EQUIPPED WITH DOUBLE-ROW HIGH-PRESSURE HEATERS
Performance study on water drenching filler with modified small spacing in cooling towers
Thermal performance analysis on geothermal-solar power generation system
Related Author
ZHAO Shunan
CHEN Yuling
HU Sanji
AN Hong-xinXi'an Thermal Power Insititute Co Ltd
ZHONG Ping
YAO Xiao-lin
ZHU Li-tong
SHI Yan-zhou
Related Institution
China Academy of Water Resources and Hydropower Research
College of Energy, Power and Mechanical Engineering, North China Electric Power University
Shenhua Guohua (Beijing) Electric Power Research Institute Co., Ltd
Baoding Huadian Electric Power Design and Research Institute Co., Ltd
Key Laboratory of Power Station Equipment Status Monitoring and Control, Ministry of Education, North China Electric Power University