MAO Mingce, WANG Juan, HU Jinbao. Temperature inversion in summer daytime and its influence on heat dissipation of dry cooling tower[J]. Thermal power generation, 2020, 49(11): 147-152.
DOI:
MAO Mingce, WANG Juan, HU Jinbao. Temperature inversion in summer daytime and its influence on heat dissipation of dry cooling tower[J]. Thermal power generation, 2020, 49(11): 147-152. DOI: 10.19666/j.rlfd.202001090.
Temperature inversion in summer daytime and its influence on heat dissipation of dry cooling tower
摘要
为了优化间接空冷塔(间冷塔)设计参数
适应夏季昼间高温低风速时段对间冷塔散热的不利影响
对渭南市某间接空冷项目开展夏季系留气球低空探测
用Fluent软件模拟了逆温对间冷塔散热的影响。结果表明:入口高度、出口高度接地逆温强度每增强1.0℃/(100 m)
In order to optimize the design parameters of indirect air cooling tower
make the tower adaptive to the adverse effect of high temperature and low wind speed in summer daytime on its heat dissipation
low altitude detection of captive balloon in summer was carried out for an indirect air cooling project in Weinan
and the influence of temperature inversion on heat dissipation the indirect cooling tower is simulated by computational fluid dynamic(CFD) software. The result shows that
the heat dissipation of the tower reduces by 2.4% and 3.0% for each 1.0 ℃/(100 m) increase in intensity of ground temperature inversion
according to the top height of ground temperature inversion
inlet level(≤50 m) and outlet level(≤100 m). The suspended inversion is observed during high temperature and low wind speed period in summer daytime
it accelerates the heat dissipation capacity of the tower than upper from the intension of 0.5~2.0 ℃/(100 m) within the thickness of 100 m
but the influence of other thickness needs more work. At last
it is strong suggested to increase observe times and height during the time of high temperature in daytime when the temperature inversion is investigated in summer.