TANG Lei, LIU Yanxue, HE Suoying, et al. Experimental study on effect of ambient crosswind on performance of large counter-flow cooling towers[J]. Thermal power generation, 2020, 49(6): 144-151.
DOI:
TANG Lei, LIU Yanxue, HE Suoying, et al. Experimental study on effect of ambient crosswind on performance of large counter-flow cooling towers[J]. Thermal power generation, 2020, 49(6): 144-151. DOI: 10.19666/j.rlfd.201912287.
Experimental study on effect of ambient crosswind on performance of large counter-flow cooling towers
Counter flow natural ventilation cooling towers are susceptible to environmental winds
resulting in performance deterioration.Based on the relevant industry standards
this paper conducted a real tower test on the inlet and outlet parameters of a natural ventilation wet counterflow tower for an active power plant.It carried out a comprehensive monitoring of the cooling tower's inlet and outlet parameters
including the dry and wet bulb temperature of the air at tower inlet
water temperature at tower inlet
air temperature at tower outlet
water temperature at tower outlet and the temperature above and under the packing.Through collation of the cooling tower test data
the ventilation and thermal performance of the cooling tower was analyzed
and characteristics of the cooling tower in summer were analyzed specially.Moreover
the effects of optimization measures such as air deflectors
air ducts
and non-uniform arrangement of packing on the cooling tower ventilation and thermal performance were compared and analyzed.The results show that
the presence of cross wind affected the circumferential air entrance
resulting in uneven temperature above the water separator for cooling tower.The performance of the cooling tower can be improved by installing air deflectors
air ducts
and non-uniform arrangement of packing.Taking the high-speed flow condition with double-pump in summer as an example
when the wind speed reached 3.2 m/s
the uniformity of the inlet air increased by 36.7%
and the temperature uniformity above the water separator increased by 10.5%.When the wind speed was close to 4 m/s
the cooling performance improved by 8.7%.The result has certain reference value for structural improvement of cooling towers in similar power plants.
CORRELATION BETWEEN TEST COEFFICIENTS OF INDUSTRIAL COOLING TOWER AND SIMULATED TESTING TOWER
MEASUREMENT AND CALCULATION METHOD FOR THERMAL PERFORMANCE TEST OF ULTRA-SUPERCRITICAL UNIT WITH STEAM TURBINE EQUIPPED WITH DOUBLE-ROW HIGH-PRESSURE HEATERS
Performance study on water drenching filler with modified small spacing in cooling towers
Thermal performance analysis on geothermal-solar power generation system
Study on thermal performance of double-turbine regeneration system in double-reheat unit
Related Author
CHEN Yuling
HU Sanji
AN Hong-xinXi'an Thermal Power Insititute Co Ltd
ZHONG Ping
YAO Xiao-lin
ZHU Li-tong
SHI Yan-zhou
CHEN Yuling Xi'an Thermal Power Research Institute Co.
Related Institution
Xi'an Thermal Power Research Institute Co., Ltd
College of Energy, Power and Mechanical Engineering, North China Electric Power University
Shenhua Guohua (Beijing) Electric Power Research Institute Co., Ltd
Baoding Huadian Electric Power Design and Research Institute Co., Ltd
Key Laboratory of Power Station Equipment Status Monitoring and Control, Ministry of Education, North China Electric Power University