Experimental study on resistance characteristics of water collecting devices with U-type channel under dry/wet condition in high-level water collecting cooling towers
|更新时间:2025-09-28
|
Experimental study on resistance characteristics of water collecting devices with U-type channel under dry/wet condition in high-level water collecting cooling towers
Thermal Power GenerationVol. 49, Issue 2, Pages: 77-82(2020)
LONG Guoqing, ZHANG Zhiyu, TANG Dongsheng, et al. Experimental study on resistance characteristics of water collecting devices with U-type channel under dry/wet condition in high-level water collecting cooling towers[J]. Thermal power generation, 2020, 49(2): 77-82.
DOI:
LONG Guoqing, ZHANG Zhiyu, TANG Dongsheng, et al. Experimental study on resistance characteristics of water collecting devices with U-type channel under dry/wet condition in high-level water collecting cooling towers[J]. Thermal power generation, 2020, 49(2): 77-82. DOI: 10.19666/j.rlfd.201910226.
Experimental study on resistance characteristics of water collecting devices with U-type channel under dry/wet condition in high-level water collecting cooling towers
摘要
随着高位收水冷却塔的快速发展
为了更好地优化塔内流场
提高冷却塔的冷却效率
对高位塔中收水装置阻力特性的研究愈加必要。本文针对实验工况设计了风洞实验装置
对一种典型的U型收水装置在风洞中进行了模型实验。在不同空气流速下
研究对比了有/无水工况下收水装置的阻力特性
发现有水工况阻力明显大于无水工况的阻力。随后
利用数值模拟研究了空气流场
并分别提出了有/无水工况下阻力系数与雷诺数的关系。最后
对有水工况下的阻力系数计算公式进行了修正
使其能够为实际高位塔的阻力计算提供依据。
Abstract
With the rapid development of high-level water collecting cooling towers
in order to better optimize the flow field inside the tower and improve the cooling efficiency of the cooling tower
it is necessary to study the resistance characteristics of the water collecting device in the high-level tower. In this paper
a wind tunnel experimental apparatus was designed according to the test conditions
and the model experiments of typical U-type water collecting devices were carried in the wind tunnel. The resistance characteristics of the water collecting device was investigated at different air velocities under dry/wet conditions. It is found that the resistance under wet condition is significantly greater than that under dry condition. Then
the air field is studied by simulation
and the relationship between resistance coefficient and Reynolds number under dry/wet conditions is proposed. Finally
the formula of resistance coefficient under wet condition is modified to provide basis for calculating the resistance of high-level water collecting cooling towers.