Influence of turbine generator set parameters on system damping
a unified system linearization model for subsynchronous oscillation and low frequency oscillation analysis is established and properly simplified.The shaft model
steam turbine and governor
generator and its excitation system and transmission line model are included.The complex torque coefficient approach is adopted to analyze the system’s mechanical damping and mechanical damping characteristics.Different parameter configurations have different influences on the system’s damping characteristics
the effects of governor system parameters
such as time constant of servomotor position feedback T_2
governor speed feedforward coefficient K_2
time constant of turbine high pressure volume T_(cs) and time constant of reheater steam volume T_(rhs)
as well as the electric parameters
are mainly considered.The results show that
the effects of the governor parameters on the system’s damping characteristics focus on low frequency range
while that of the electric parameters focus on subsynchronous frequency range.The results of the study can provide the basis for inhibiting low frequency oscillation and secondary synchronous oscillation of the power systems.