Fault diagnosis and treatment of low frequency vibration of high and medium pressure rotor in a supercritical 630 MW steam turbine
摘要
针对某电厂超临界630 MW机组通流改造后出现顺序阀工况下振动大、振幅波动大、低频分量大等异常现象
通过对机组汽轮机振动故障诊断管理(TDM)系统图谱特征进行分析
判断故障原因为轴颈测量表面不平、轴瓦载荷轻、剩余汽流力造成的随机振动所致。对此
通过采取更换振动探头测量位置、增加轴瓦载荷、优化阀序等方法
最终将振动值降低到合格范围。本文方法对同类型机组类似的振动故障诊断和处理具有一定借鉴意义。
Abstract
After flow reformation of a supercritical 630 MW unit in a power plant
the abnormal phenomena of large vibration
large amplitude fluctuation and large low-frequency component are analyzed in the operation of sequence valve. By analyzing the spectroscopic characteristics of the vibration diagnosis system of the steam turbine
the failure are judged as the random vibration caused by the rough shaft surface
the light bearing load and the residual steam flow force. Through changing the position of vibration probe
increasing the bearing load and optimizing the valve open sequence and other methods
the vibration amplitude is eventually reduced to the acceptable range. This method in this study has certain referential significance for fault diagnosis and treatment of the same type units.
SIMPLIFIED FINITEELEMENT CALCULATION MODEL OF TEMPERATURE FIELD FOR STEAM TURBINE ROTOR
APPLICATION OF SOLID SELF-LUBRICATING TECHNOLOGY IN POWER PLANTS
STUDY ON CONTROL SYSTEM SETTING OF DOUBLE EXTRACTION ADJUSTABLE STEAM TURBINE
ANALYSIS OF FAULTS OCCURRED IN SYNCHRONIZATION WITH POWER NETWORK FOR TAKING INITIAL LOAD BY STEAM TURBINE OF A 180MW GAS AND STEAM TURBINE COMBINED CYCLE UNIT
CAUSE ANALYSIS AND IMPROVEMENT MEASURES FOR PRESSURE REDUCTION OF LUBRICANT OIL DURING STARTUP OF 300MW UNITS