Wide-load regenerative technology of No.0 high-pressure heater in an ultra supercritical 1 000 MW unit
an ultra-supercritical 1 000 MW unit of a power generation company is taken as an example to study the layout
control strategy of No.0 high-pressure heater and its influence on the temperature of boiler feed water
heat consumption and the running rate of selective catalyst reduction(SCR) denitration system. The results show that
in the premise of guaranteeing feed water owes enthalpy at the export of economizer under low-load
with the proper control of steam pressure behind the No.0 extraction control valve
the application of the No.0 highpressure heater can increase the temperature of boiler feed water under medium and low loads and stabilize the temperature of boiler feed water at 290 ℃ under medium and high loads. The inlet flue gas temperature at SCR system under medium and low loads can also be increased and kept at the efficient reaction temperature range of the catalyst
which can improve the running rate of the denitration system and have good environmental protection value. Meanwhile
the reasonable No.0 extraction steam parameters could reduce the unit heat consumption under medium and high loads
which has great energy-saving value. This conclusion is of guidance and reference for the application
commercial operation
addition and retrofit of the No.0 high-pressure heater of the same type new units.