Optimization and adjustment of reheater tube wall temperature with reheater steam temperature of 623℃
a 1 000 MW unit and a 1 000 MW double reheat unit with reheat steam temperature of 623 ℃ as research object. The causes of low reheat steam temperature are comprehensively analyzed. And the targeted optimization and adjustment are carried out. After optimization
the reheat steam temperature are greatly increased. The reheat steam temperatures of 660 MW unit and 1 000 MW unit are increased from 609.0 ℃ and 599.8 ℃ to 618.0 ℃ and 619.8 ℃
respectively. The reheat steam temperatures of high and low temperature reheater of 1 000 MW unit are increased from 603.4 ℃ and 601.4 ℃ to 612.5 ℃and 612.7 ℃
respectively. At the same time
the deviation of high and low temperatures of final reheater tube wall are decreased. This results provide references for the optimization and adjustment of unit reheater tube wall temperature of the same type unit.