SIMULATION AND ANALYSIS ABOUT WORN-OUT ON CONNECTING PIPE OF LOW-PRESSURE REHEATER FOR A BOILER OF 600 MW UNIT
the simulation and analysis of worn-out on connecting pipe bundle of low-pressure reheater nearby the furnace outlet suffured from gas-phase flow field distribustion
movement of flyash
and concentration distribution etc.in the flue duct of boiler concerning 600 MW unit have been carried out.Results show that the flue gas velocity
particle's concentration and average collision velocity of particles nearby the furnace outlet all are larger due to influence of solid-gas two-phase flow distribution in the flue duct
thereby
the velocity of wornout on connecting pipes of the low-pressure reheater is also larger.It is recommended to install wornout-resistant covers of 6 mm thickness onto the windward surface of horizontal I-shaped pipe bundle of the low-pressure reheater between bottom of the first row connecting pipe and the other connecting pipes
as well as installing wornout-resitant covers with 3 mm thickness onto the other remained parts.