ZHAO Yong1, CHENG Yong-hong2, GUO Liang21.Xi'an Thermal Power Research Institute Co Ltd. MEASUREMENT OF WEAK DC SIGNAL IN ON-LINE MONITORING SYSTEM OF XLPE POWER CABLES[J]. Thermal power generation, 2008, (9): 79-82.
DOI:
ZHAO Yong1, CHENG Yong-hong2, GUO Liang21.Xi'an Thermal Power Research Institute Co Ltd. MEASUREMENT OF WEAK DC SIGNAL IN ON-LINE MONITORING SYSTEM OF XLPE POWER CABLES[J]. Thermal power generation, 2008, (9): 79-82. DOI: 10.19666/j.rlfd.2008.09.023.
MEASUREMENT OF WEAK DC SIGNAL IN ON-LINE MONITORING SYSTEM OF XLPE POWER CABLES
The design of key modules and digital filters for measuring circuit of weak DC signals in on-line monitoring system of XLDE power cables has been studied
the results of performance test for the said measuring circuit show that the designed scheme of the measuring circuit can more accurately measure the DC signals of about 1 nA
the average error being 2.25%
satisfying the requirements of monitoring system for signal precission.